Plan Review Notes
Plan Review Notes For Permit 19111204
Permit Number 19111204
Review Stop M
Sequence Number 3
Notes
Date Text
2020-04-28 15:05:213RD REVIEW FBC-2017
 PERMIT #19111204
 4/28/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL COMMENT RESPONSE DOCUMENT DATED
 4/14/2020 DOES NOT BEAR THE NAME OF THE ENGINEER,
 ARCHITECT, CONTRACTOR, QUALIFIER OR OTHER PERSON TO
 IDENTIFY WHO PREPARED THE DOCUMENT AND PROVIDED THE
 RESPONSES. A) ITEM #3 IN THE RESPONSE DOCUMENT
 INDICATES THE CONTRACTOR SHALL INSURE THERE IS A DRAIN
 ON THE FLOOR OF THE GENERATOR ROOM TO REMOVE ANY WATER
 ON THE FLOOR TO THE OUTSIDE. PLEASE CLARIFY IF THERE IS
 AN EXISTING FLOOR DRAIN IN THE ROOM IN PROXIMITY OF THE
 RADIATOR SHROUD OR IF A NEW DRAIN WILL BE INSTALLED.
  
 2) ALTERNATE APPROVAL LETTER FOR MECHANICAL: A) PROVIDE
 EVIDENCE THAT THE ALTERNATIVE MESH SCREEN WHICH
 INCLUDES A CHAIN LINK FENCE IS EQUIVALENT TO A
 MANUFACTURED LOUVER IN CORROSION RESISTANCE, AND IN
 PREVENTING WATER INTRUSION- SEE SECTION 501.3.2 FBC M:
 "EXHAUST OPENINGS THAT TERMINATE OUTDOORS SHALL BE
 PROTECTED WITH CORROSION-RESISTANT SCREENS, LOUVERS OR
 GRILLES. OPENINGS IN SCREENS, LOUVERS AND GRILLES SHALL
 BE SIZED NOT LESS THAN 1/4 INCH (6.4 MM) AND NOT LARGER
 THAN 1/2 INCH (12.7 MM). OPENINGS SHALL BE PROTECTED
 AGAINST LOCAL WEATHER CONDITIONS. LOUVERS THAT PROTECT
 EXHAUST OPENINGS IN STRUCTURES LOCATED IN
 HURRICANE-PRONE REGIONS, AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING, SHALL COMPLY WITH AMCA
 STANDARD 550. OUTDOOR OPENINGS LOCATED IN EXTERIOR
 WALLS SHALL MEET THE PROVISIONS FOR EXTERIOR WALL
 OPENING PROTECTIVES IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING." B) THE LETTER THAT IS
 INDICATED TO BE FROM CATERPILLAR IS NOT FROM
 CATERPILLAR COMPANY BUT IS AN EMAIL FROM A MR. ROBERT
 BUTT WHO IS EMPLOYED BY PANTROPIC POWER, THEREFORE NOT
 ACCEPTABLE EVIDENCE OF COMPLIANCE PER MANUFACTURER'S
 GUIDELINES AND SPECIFICATIONS. C) SHEETS M-201, A-002,
 A-005: THE EXHAUST LOUVER IS NOT CALLED OUT ON THE
 MECHANICAL PLAN AND IS IDENTIFIED AS TYPICAL CHAIN LINK
 FENCE DETAIL ON THE ARCHITECTURAL PLANS. PLEASE
 PROPERLY IDENTIFY THE EXHAUST SCREEN PROPERLY TO
 CORRELATE WITH THE THE ALTERNATE APPROVAL REQUEST.
 AT THIS TIME THERE IS NOT ENOUGH EVIDENCE TO PROVE THAT
 THE PROPOSED EXHASUT SCREEN DESIGN IS EQUIVALENT OF
 THAT PRESCRIBED IN THIS CODE IN QUALITY, STRENGTH,
 EFFECTIVENESS, FIRE RESISTANCE, DURABILITY AND SAFETY-
 SEE SECTION 104.11 FBC B.
  
 3) SHEETS A-002, A-003, M-201: THE NORTH ELEVATION VIEW
 AND THE FAN INSTALLATION DETAILL DO NOT INDICATE THE
 LV-3 AND LV-4 LOUVERS TO BE INSTALLED OVER INTAKE FANS
 SAF-1 AND SAF-2 AS IS INDICATED ON SHEET M201. PLEASE
 REVIEW COMMENT #2 FROM THE 1ST REVIEW COPIED BELOW.
 M-201 & M-401: THE DETAIL SHOWING THE ATTACHMENT OF THE
 LOUVERS DIRECTLY TO SAF 1 & 2 MAY NOT BE CONSISTENT
 WITH THE APPROVED INSTALLATION DETAILS SHOWN IN THE
 MIAMI-DADE NOA FOR THE LOUVER. PLEASE SUBMIT TWO COPIES
 OF THE NOA WITH APPLICABLE INSTALLATION DETAILS CIRCLED
 OR HIGHLIGHTED.
 THE LOUVER NOA HAS BEEN SUBMITTED HOWEVER NO ATTACHMENT
 DETAILS HAVE BEEN MARKED. PLEASE NOTE THAT THE LOUVER
 SPECIFIES ATTACHMENT INTO STRUCTURAL SUBSTRATES AND
 ALSO SPECIFIES TYPES AND SIZES OF FASTENERS, SPACING OF
 FASTENERS, EDGE DISTANCE CLEARANCES, AND DEPTHS OF
 EMBEDMENT. ALL OF THESE DETAILS MUST BE CALLED OUT BY
 THE EOR.
  
 4) THE ENGINE EXHAUST PIPING TERMINATIONS ON THE
 DRAWINGS APPEAR TO BE OPEN TO WATER INTRUSION. ARE
 THESE ACTUAL FIELD CONDITIONS OR JUST A RENDERING? ARE
 THE EXHAUST PIPES BEING REPLACED? HOW ARE THEY
 SUPPORTED? PLEASE PROVIDE SPECIFIC DETAILS TO ADDRESS
 THESE ISSUES- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 [email protected]
  