| 2020-05-03 14:26:03 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19111204 |
| | ADD: 6329 N. JOG RD. |
| | CONT: ALL-SITE CONSTRUCTION INC. |
| | TEL: 561-848-1110 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MARCH27TH- MAY 03RD/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) SEMI-COMPLIED. THE DESIGNER OF RECORD HAS RESPONDED |
| | TO THIS ROUND OF COMMENTS, THANK YOU. THERE IS GOING TO |
| | BE A QUESTION LATER IN THIS REVIEW ABOUT THE ALTERNATE |
| | MATERIALS & METHODS REQUEST, HOW TO SUBMIT. |
| | |
| | 2A) 3RD REQUEST SEMI-COMPLIED. THIS EXTERIOR DOOR |
| | TESTING REPORT MANUFACTURER PHILADELPHIA HARDWARE GROUP |
| | (PHG) IS FOR A STEEL EXTERIOR DOOR, 5 PAGES LONG. THIS |
| | DOCUMENT ALONE DOES NOT MEET THE REQUIREMENTS FORM THE |
| | STATE OF FLORIDA FOR A PRODUCT APPROVAL. |
| | THERE ARE NO DOCUMENTS SUBMITTED FOR THE INDEPENDENT |
| | 3RD PARTY CERTIFICATION REQUIRED BY THE STATE FOR A |
| | STATE APPROVAL OR FOR A LOCAL WEST PALM BEACH LOCAL OR |
| | SITE PRODUCT APPROVAL. |
| | |
| | 2A)2ND REQUEST. SHEET C001 SHOWS ONE NEW EXTERIOR DOOR |
| | AND NEW DEMOLITION FOR DOOR OPENING, AND ONE EXTERIOR |
| | REPLACEMENT DOOR. SEE SHEET A002 ELEVATION, PROPOSED |
| | NEW DOOR. . FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010. |
| | PLEASE PROVIDE PRODUCT APPROVALS FOR EACH OF THE |
| | COMPONENTS/ CLADDING LISTED BELOW. 2017 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS , |
| | |
| | 2B) 3RD REQUEST. SEMI-COMPLIED. THERE IS A MIAMI-DADE |
| | NOA 17-0919.04 SUBMITTED. SINCE THERE ARE 2 ISSUES WITH |
| | LOUVERED OPENINGS WE NEED TO HAVE LISTED ON THE NOA FOR |
| | WHICH OPENINGS THIS PRODUCT IS GOING TO BE SUBMITTED |
| | FOR? 2ND IT ALSO NEEDS TO BE UNDERSTOOD THAT THERE IS A |
| | LETTER TO BE SUBMITTED FOR THE GENERATOR EXHAUST. OUR |
| | INSPECTORS ARE NOT ALWAYS AWARE OF THE COMMENTS DURING |
| | PLAN REVIEW AND LOCATIONS EACH PRODUCT APPROVAL CAN OR |
| | CANNOT BE INSTALLED. |
| | 2ND REQUEST, THIS NEEDS TO BE ADDRESSED BY THE ENGINEER |
| | OF RECORD. NOTE IF LOUVERS ARE TO BE INSTALLED AS |
| | INTAKE OR EXHAUST LOUVERS AND THE PRESSURES THAT WILL |
| | BE EXERTED ON THE LOUVER WHEN IN USE, IS THIS PRESSURE |
| | GOING TO BE GREATER THAN THAT OF PRESSURES DESIGN |
| | PRESSURES FOR HIGH WIND EVENTS? 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2C-2D) COMPLIED. |
| | |
| | 2E) COMPLIED.5/18/2020. E-MAIL SENT TO |
| | [email protected] |
| | REQUEST FOR ALTEERNATE MATERIALS & METHODS. BUILDING |
| | OFFICIAL BELIEVES WITH THE SUBMITTED DOCUMENTS & |
| | CALCULATIONS THAT IS SUFFICIENT TO MEET THE ENTENT OF |
| | THE CODE. ALTERNANTE MATERIALS & METHODS WOULD NOT NEED |
| | TO BE USED. WE WILL STILL NEED THE SUBMITTED DOCUMENTS |
| | TO SUBSTANUATE CODE COMPLIANCE. |
| | |
| | NEW COMMENT: 5/03/2020. THIS COMMENT DEALS WITH THE |
| | REQUEST FOR ALTERNATE MATERIALS & METHOD REQUEST FOR |
| | THE GENERATOR EXHAUST REQUIREMENTS INSTEAD OF A LOUVER |
| | REQUIRED UNDER COMPONENTS AND CLADDING REQUIREMENTS OF |
| | THE FBC-B 6TH EDITION. I SENT AN E-MAIL ( 4-27-2020) |
| | .TO MY SUPERVISOR SAMANTHA HILL & ASSISTANT BUILDING |
| | OFFICIAL DYLAN BATTLES ABOUT THIS REQUEST. MS. HILL HAS |
| | BEEN IN CONTACT WITH MS. FELICIA SAFFOLD ABOUT WHAT IS |
| | REQUIRED FOR AN ALTERNATE MATERIALS, METHODS DESIGN AND |
| | METHODS OF CONSTRUCTION AND EQUIPMENT 104.11 OF THE |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE |
| | 6TH EDITION, CHAPTER 1, ADMINISTRATION. MS. SAFFOLD |
| | INDICATED BY E-MAIL THAT THEY WOULD BE APPLYING SHORTLY |
| | FOR ALTERNATE MATERIALS & METHODS. THIS REQUEST SHOULD |
| | BE ADDRESSED TO THE BUILDING OFFICIAL ROBERT BROWN. |
| | |
| | 3) SEMI-COMPLIED, NO EXTERIOR DOOR PRODUCT APPROVALS |
| | WERE SUBMITTED. 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE |
| | CODE SECTION 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 4) SEMI-COMPLIED. SEE COMMENT 2A. |
| | |
| | 5) PROVISO: SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L |
| | 4X4 SS FRAME AROUND THE INTAKE FANS PLEASE SHOW |
| | COMPLIANCE WITH: |
| | WELDED OR BOLTED CONNECTIONS |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| | AMERICAN WELDING SOCIETY. |
| | 2017 FBC-B 2204.1 WELDING |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS |
| | FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING |
| | INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. |
| | |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |