Plan Review Notes
Plan Review Notes For Permit 19111204
Permit Number 19111204
Review Stop B
Sequence Number 3
Notes
Date Text
2020-05-03 14:26:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19111204
 ADD: 6329 N. JOG RD.
 CONT: ALL-SITE CONSTRUCTION INC.
 TEL: 561-848-1110
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MARCH27TH- MAY 03RD/ 2020
 ACTION: DENIED
  
 1) SEMI-COMPLIED. THE DESIGNER OF RECORD HAS RESPONDED
 TO THIS ROUND OF COMMENTS, THANK YOU. THERE IS GOING TO
 BE A QUESTION LATER IN THIS REVIEW ABOUT THE ALTERNATE
 MATERIALS & METHODS REQUEST, HOW TO SUBMIT.
  
 2A) 3RD REQUEST SEMI-COMPLIED. THIS EXTERIOR DOOR
 TESTING REPORT MANUFACTURER PHILADELPHIA HARDWARE GROUP
 (PHG) IS FOR A STEEL EXTERIOR DOOR, 5 PAGES LONG. THIS
 DOCUMENT ALONE DOES NOT MEET THE REQUIREMENTS FORM THE
 STATE OF FLORIDA FOR A PRODUCT APPROVAL.
 THERE ARE NO DOCUMENTS SUBMITTED FOR THE INDEPENDENT
 3RD PARTY CERTIFICATION REQUIRED BY THE STATE FOR A
 STATE APPROVAL OR FOR A LOCAL WEST PALM BEACH LOCAL OR
 SITE PRODUCT APPROVAL.
  
 2A)2ND REQUEST. SHEET C001 SHOWS ONE NEW EXTERIOR DOOR
 AND NEW DEMOLITION FOR DOOR OPENING, AND ONE EXTERIOR
 REPLACEMENT DOOR. SEE SHEET A002 ELEVATION, PROPOSED
 NEW DOOR. . FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010.
 PLEASE PROVIDE PRODUCT APPROVALS FOR EACH OF THE
 COMPONENTS/ CLADDING LISTED BELOW. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,
  
 2B) 3RD REQUEST. SEMI-COMPLIED. THERE IS A MIAMI-DADE
 NOA 17-0919.04 SUBMITTED. SINCE THERE ARE 2 ISSUES WITH
 LOUVERED OPENINGS WE NEED TO HAVE LISTED ON THE NOA FOR
 WHICH OPENINGS THIS PRODUCT IS GOING TO BE SUBMITTED
 FOR? 2ND IT ALSO NEEDS TO BE UNDERSTOOD THAT THERE IS A
 LETTER TO BE SUBMITTED FOR THE GENERATOR EXHAUST. OUR
 INSPECTORS ARE NOT ALWAYS AWARE OF THE COMMENTS DURING
 PLAN REVIEW AND LOCATIONS EACH PRODUCT APPROVAL CAN OR
 CANNOT BE INSTALLED.
 2ND REQUEST, THIS NEEDS TO BE ADDRESSED BY THE ENGINEER
 OF RECORD. NOTE IF LOUVERS ARE TO BE INSTALLED AS
 INTAKE OR EXHAUST LOUVERS AND THE PRESSURES THAT WILL
 BE EXERTED ON THE LOUVER WHEN IN USE, IS THIS PRESSURE
 GOING TO BE GREATER THAN THAT OF PRESSURES DESIGN
 PRESSURES FOR HIGH WIND EVENTS? 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2C-2D) COMPLIED.
  
 2E) COMPLIED.5/18/2020. E-MAIL SENT TO
 [email protected]
 REQUEST FOR ALTEERNATE MATERIALS & METHODS. BUILDING
 OFFICIAL BELIEVES WITH THE SUBMITTED DOCUMENTS &
 CALCULATIONS THAT IS SUFFICIENT TO MEET THE ENTENT OF
 THE CODE. ALTERNANTE MATERIALS & METHODS WOULD NOT NEED
 TO BE USED. WE WILL STILL NEED THE SUBMITTED DOCUMENTS
 TO SUBSTANUATE CODE COMPLIANCE.
  
 NEW COMMENT: 5/03/2020. THIS COMMENT DEALS WITH THE
 REQUEST FOR ALTERNATE MATERIALS & METHOD REQUEST FOR
 THE GENERATOR EXHAUST REQUIREMENTS INSTEAD OF A LOUVER
 REQUIRED UNDER COMPONENTS AND CLADDING REQUIREMENTS OF
 THE FBC-B 6TH EDITION. I SENT AN E-MAIL ( 4-27-2020)
 .TO MY SUPERVISOR SAMANTHA HILL & ASSISTANT BUILDING
 OFFICIAL DYLAN BATTLES ABOUT THIS REQUEST. MS. HILL HAS
 BEEN IN CONTACT WITH MS. FELICIA SAFFOLD ABOUT WHAT IS
 REQUIRED FOR AN ALTERNATE MATERIALS, METHODS DESIGN AND
 METHODS OF CONSTRUCTION AND EQUIPMENT 104.11 OF THE
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE
 6TH EDITION, CHAPTER 1, ADMINISTRATION. MS. SAFFOLD
 INDICATED BY E-MAIL THAT THEY WOULD BE APPLYING SHORTLY
 FOR ALTERNATE MATERIALS & METHODS. THIS REQUEST SHOULD
 BE ADDRESSED TO THE BUILDING OFFICIAL ROBERT BROWN.
  
 3) SEMI-COMPLIED, NO EXTERIOR DOOR PRODUCT APPROVALS
 WERE SUBMITTED. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE
 CODE SECTION 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) SEMI-COMPLIED. SEE COMMENT 2A.
  
 5) PROVISO: SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L
 4X4 SS FRAME AROUND THE INTAKE FANS PLEASE SHOW
 COMPLIANCE WITH:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  