| Plan Review Notes For Permit 19111204 |
| Permit Number |
19111204 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-03-23 10:25:16 | REVIEWED BY JAMES BAKER, PE | | | | | | FAILED SEE COMMENTS BELOW: | | | 1) 2017 FMC 501.3.2 EXHAUST OPENING PROTECTION. THE | | | CHAIN LINK FENCE PROPOSED MUST HAVE OPENINGS NO LARGER | | | THAN 1/2INCH AND NO SMALLER THAN 1/4INCH. PLEASE | | | INDICATE ON DRAWINGS. | | | | | | | | | 2) 2017 FBC 107.2.1 CONFIRM AND PROVIDE LETTER FROM | | | GENERATOR MANUFACTURER THAT BARRIER WALL WILL NOT | | | IMPEDE THE EXHAUST AIRFLOW TO THE POINT OF CAUSING | | | EXCESSIVE HEAT BUILD UP IN GENERATOR AND EXCESSIVE LOSS | | | OF EFFICIENCY. | | | | | | | | | 3) 2017 FBC 107.2.1 FURTHER EVALUATE ANY POTENTIAL FOR | | | RAIN PENETRATION THROUGH THE 1/2 CHAIN LINK FENCE INTO | | | THE DUCTWORK ATTACHING THE GENERATOR EXHAUST TO THE | | | OPENING. SUGGEST CONSULTING THE GENERATOR ENGINEERING | | | DEPARTMENT. | | | | | | 561-805-6724 |
|