Plan Review Notes
Plan Review Notes For Permit 19111204
Permit Number 19111204
Review Stop B
Sequence Number 2
Notes
Date Text
2020-03-12 07:44:042017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19111204
 ADD: 6329 N. JOG RD.
 CONT: ALL-SITE CONSTRUCTION INC.
 TEL: 561-848-1110
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. MARCH12TH/ 2020
 ACTION: DENIED
  
 NOTICE ONLY!!!!!!!! 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
 1) 2ND REQUEST. THE RESPONSE INDICATES THE WIND DESIGN
 CRITERIA CAN BE FOUND ON SHEET S-001 REVISION # 1.
 PLEASE NOTE THERE WERE NO NEW SHEETS ADDED OR REVISION
 IN THE ARCHITECTURAL OR STRUCTURAL SHEETS. PLEASE ALSO
 NOTE THE REVIEW COMMENTS LOOK LIKE THEY WERE DEVELOPED
 BY THE CONTRACTOR (ALL-SITE CONSTRUCTION, INC.) AND NOT
 THE DESIGNER OF RECORD FOR THIS PROJECT.
 1ST REVIEW COMMENT. THE DEMOLITION, ARCHITECTURAL AND
 STRUCTURAL SHEETS ALL SHOW NEW COMPONENTS AND CLADDING
 TO THE EXTERIOR OF THE BUILDING, BUT THERE IS NO WIND
 DESIGN CRITERIA GIVEN. 2017 FBC-B 1603.1.4 WIND DESIGN
 DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS.
  
 1.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1.7 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 1.8 IT WOULD APPEAR THE NEW AND REPLACEMENT EXTERIOR
 DOORS ARE IN THE WALL ZONE 5, HIGHER PRESSURES.
  
 2A) 2ND REQUEST. SHEET C001 SHOWS ONE NEW EXTERIOR DOOR
 AND NEW DEMOLITION FOR DOOR OPENING, AND ONE EXTERIOR
 REPLACEMENT DOOR. SEE SHEET A002 ELEVATION, PROPOSED
 NEW DOOR.
 PLEASE PROVIDE PRODUCT APPROVALS FOR EACH OF THE
 COMPONENTS/ CLADDING LISTED BELOW. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,
  
 2B) 2ND REQUEST, THIS NEEDS TO BE ADDRESSED BY THE
 ENGINEER OF RECORD. NOTE IF LOUVERS ARE TO BE INSTALLED
 AS INTAKE OR EXHAUST LOUVERS AND THE PRESSURES THAT
 WILL BE EXERTED ON THE LOUVER WHEN IN USE, IS THIS
 PRESSURE GOING TO BE GREATER THAN THAT OF PRESSURES
 DESIGN PRESSURES FOR HIGH WIND EVENTS? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2C) 2ND REQUEST. WITHIN THE GENERATOR ROOM WHEN THE
 GENERATOR IS RUNNING WILL THE PRESSURES WITHIN THIS
 ROOM BE NEUTRAL TO WHERE YOU WILL BE ABLE TO OPEN THE
 EXTERIOR MAN DOOR AS WELL AS THE DOUBLE DOORS TO THE
 NEW SWITCH GEAR? 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2D) 2ND REQUEST. THE SAME CONCERN OF WHAT TYPE OF
 PRESSURES WILL BE EXERTED ON THE NEW PROPOSED 2 HR.
 FIRE RATED WALLS. PLEASE PROVIDE THE DEFLECTION
 LIMITATIONS FOR THE NEW WALL SEE THE 2017 FBC-B TABLE
 1604.3.
  
 3) SEMI-COMPLIED, NO EXTERIOR DOOR PRODUCT APPROVALS
 WERE SUBMITTED. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE
 CODE SECTION 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) NO PRODUCT APPROVALS WERE SUBMITTED FOR THE NEW
 DOOR. WITHIN ALL OF THE PRODUCT APPROVALS PLEASE CIRCLE
 ALL RELATIVE SECTIONS THAT PERTAIN TO THE SITE SPECIFIC
 INSTALLATION INCLUDING PRESSURES, ANCHORS, SPACING OF
 ANCHORS, ETC. 2017 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 5) PROVISO: SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L
 4X4 SS FRAME AROUND THE INTAKE FANS PLEASE SHOW
 COMPLIANCE WITH:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  