| 2019-12-27 11:21:01 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19111204 |
| | 12/27/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS D-102 & M-201: INDICATE HOW THE GENERATOR |
| | RADIATOR DISCHARGE OPENING WILL BE PROTECTED- SECTION |
| | 501.3.2 FBC M. |
| | |
| | 2) M-201 & M-401: THE DETAIL SHOWING THE ATTACHMENT OF |
| | THE LOUVERS DIRECTLY TO SAF 1 & 2 MAY NOT BE CONSISTENT |
| | WITH THE APPROVED INSTALLATION DETAILS SHOWN IN THE |
| | MIAMI-DADE NOA FOR THE LOUVER. PLEASE SUBMIT TWO COPIES |
| | OF THE NOA WITH APPLICABLE INSTALLATION DETAILS CIRCLED |
| | OR HIGHLIGHTED. |
| | |
| | 3) M-301: SUBMIT THE MIAMI- DADE NOA FOR THE EXHAUST |
| | FANS EF-1 & EF-2- RULE 9-N3 FAC. PLEASE CIRCLE OR |
| | HIGHLIGHT ALL APPLICABLE INSTALLATION DETAILS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |