2020-01-06 08:04:332017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19111204
 ADD: 6329 N. JOG RD.
 CONT: ALL-SITE CONSTRUCTION INC.
 TEL: 561-848-1110
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JAN. 6TH/ 2020
 ACTION: DENIED
  
 1) THE DEMOLITION, ARCHITECTURAL AND STRUCTURAL SHEETS
 ALL SHOW NEW COMPONENTS AND CLADDING TO THE EXTERIOR OF
 THE BUILDING, BUT THERE IS NO WIND DESIGN CRITERIA
 GIVEN. 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS.
  
 1.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1.7 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 2A) PLEASE PROVIDE PRODUCT APPROVALS FOR EACH OF THE
 COMPONENTS/ CLADDING LISTED BELOW. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,
 (C) PANEL WALLS: WALL LOUVERS FOR BOTH INTAKE AND
 EXHAUST, BOTH INTAKE AND EXHAUST FANS, WALL
 MOUNTED.
  
 2B) NOTE IF LOUVERS ARE TO BE INSTALLED AS INTAKE OR
 EXHAUST LOUVERS AND THE PRESSURES THAT WILL BE EXERTED
 ON THE LOUVER WHEN IN USE, IS THIS PRESSURE GOING TO BE
 GREATER THAN THAT OF PRESSURES DESIGN PRESSURES FOR
 HIGH WIND EVENTS? 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2C) WITHIN THE GENERATOR ROOM WHEN THE GENERATOR IS
 RUNNING WILL THE PRESSURES WITHIN THIS ROOM BE NEUTRAL
 TO WHERE YOU WILL BE ABLE TO OPEN THE EXTERIOR MAN DOOR
 AS WELL AS THE DOUBLE DOORS TO THE NEW SWITCH GEAR?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2D) THE SAME CONCERN OF WHAT TYPE OF PRESSURES WILL BE
 EXERTED ON THE NEW PROPOSED 2 HR. FIRE RATED WALLS.
 PLEASE PROVIDE THE DEFLECTION LIMITATIONS FOR THE NEW
 WALL SEE THE 2017 FBC-B TABLE 1604.3.
  
 3) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE
 SECTION 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) WITHIN ALL OF THE PRODUCT APPROVALS PLEASE CIRCLE
 ALL RELATIVE SECTIONS THAT PERTAIN TO THE SITE SPECIFIC
 INSTALLATION INCLUDING PRESSURES, ANCHORS, SPACING OF
 ANCHORS, ETC. 2017 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 5) SHEET A003 FAN SUPPORT DETAILS ALL SHOW A L 4X4 SS
 FRAME AROUND THE INTAKE FANS PLEASE SHOW COMPLIANCE
 WITH:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 6) . A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  