2019-12-02 17:46:2212/02/2019 2ND PLUMBING/ REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. ON P1 SHOWER AND TUB ARE LABELED AS FD PLEASE CHANGE
 TO CORRECT LABELS (TUB, SHOWER) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 2. SHOWER NEEDS TO BE RAN OFF THE WET VENT NOT OFF THE
 TUB DRAIN LINE PER THE 2017 FBC SEC. R3108.1 HORIZONTAL
 WET VENT PERMITTED.
 3. THE PLANS ARE NOT SIGNED BY THE ARCHITECT OF RECORD,
 SIGNATURE OF AN ARCHITECT-ENGINEER IS REQUIRED (OR
 SEAL, OR TITLE BLOCK, OR ALL THREE) ARE NOT IN
 ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471.
 4. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION 2017 FBC SEC. 2708.4, R 2713.3
 BATHTUB AND WHIRLPOOL BATHTUB VALVES. (ADD TO PLUMBING
 NOTES)
 5. SHOWER CONTROL VALVES SHALL BE PRESSURE-BALANCED,
 THERMOSTATIC-MIXING OR COMBINATION
 PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A
 HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME
 A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET
 TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN 120
 F. (ADD TO PLUMBING NOTES)
 6. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE
 LINING. THE ADJOINING WALLS AND FLOOR FRAMING ENCLOSING
 ON-SITE BUILT-UP SHOWER RECEPTORS SHALL BE LINED WITH
 ONE OF THE FOLLOWING MATERIALS. THE LINING MATERIAL
 SHALL EXTEND NOT LESS THAN 2 INCHES BEYOND OR AROUND
 THE ROUGH JAMBS AND NOT LESS THAN 2 INCHES ABOVE
 FINISHED THRESHOLDS. SHEET-APPLIED LOAD-BEARING, BONDED
 WATERPROOF MEMBRANES SHALL BE APPLIED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTRUCTIONS PER 2017 FBC SEC.
 R 2709.2.
 7. SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4"
 IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER,
 BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR
 APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO
 THE MORTAR DOES NOT COVER THEM PER MANUFACTURES
 SPECIFICATIONS.
 8. PLEASE SHOW A DETAIL OF THE SHOWER LINER
 INSTALLATION AND IF YOU ARE USING AN ALTERNATE METHOD
 IS MUST BE APPROVED AT THIS STAGE SO PROVIDE
 DOCUMENTATION FOR ALTERNATE PRODUCTS.
 9. HOT WATER RAN UNDER SLAB IN AN UN-CONDITION SPACE
 SHALL BE INSULATED PER THE 2017 FBC EC RE 403.5.3.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  