| Notes |
| Date |
Text |
| 2019-12-16 09:06:56 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE EP3 | | | | | | 1) DOES NOT LOOK TO HAVE THE MAINS GROUPED TOGETHER AS | | | REQUIRED PER 230.72 | | | | | | 2) LOAD CAL SHOWS LOAD DEVERSITY?? WHERE IS THIS | | | LOCATED IN THE CODE?? |
|