2019-12-17 10:58:062017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19111167
 ADD: 313 DATURA ST. UNIT: 101 & 102
 CONT: TRIMAR CONSTRUCTION, INC.
 TEL: 813-258-5524
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 17/ 2019
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET:
 1A) THE LIFE SAFETY NOTES INDICATE THIS OCCUPANCY IS TO
 BE CONSIDERED MERCANTILE BUT IN THE OCCUPANCY TYPE AND
 CALCS THERE 4 OCCUPANCY TYPES INDICATED, ASSEMBLY,
 MERCANTILE, BUSINESS & STORAGE. THIS TENANT SPACE IT
 WOULD APPEAR TO BE A MIXED USE OCCUPANCY. I BELIEVE THE
 AREA THAT IS LISTED AS AN ASSEMBLY OCCUPANCY IS
 MISLABELED, THE DESIGNER OF RECORD HAS NOT IDENTIFIED
 WHAT TYPE OF ASSEMBLY OCCUPANCY THIS AREA IS, A-1, A-2,
 A-3 AN ASSEMBLY OCCUPANCY DOES NOT FIT THE USE IN ANY
 OF THESE ASSEMBLY TYPES. IT APPEARS THAT THE RECEPTION
 AREA IS MORE OF A CROWD CONTROL AREA JUST AS IN SOME
 CHECK CASHING BUSINESSES, THIS AREA LENDS ITSELF TO
 MORE OF A BUSINESS OCCUPANCY OR POSSIBLY MERCANTILE.
 PLEASE REVIEW SECTIONS 303.2, 303.3 & 303.4 FOR WHAT
 USES FALL UNDER AN ASSEMBLY OCCUPANCY AND WHAT SERVICES
 FALL UNDER BUSINESS OCCUPANCIES FOUND UNDER SECTION
 304.1 OF THE 2017 FBC-B. THE OCCUPANT LOAD WILL CHANGE,
 PLEASE UPDATE THE PLANS.
  
 1B) DISCREPANCY IN THE PLANS. IT WOULD APPEAR THAT THE
 ENTRANCE AND EXIT OF THE CONTROLLED AREA ARE REVERSED.
 SHEET LS100AND A101 BOTH SHOW THE EXIT AS THE RIGHT
 OUTSWING DOOR 103A WHEREAS SHEET A105 SHOWS THE EXIT
 DOOR TO THE LEFT, PLEASE REVIEW ALL PLAN SHEETS TO
 VERIFY THE ENTRANCE AND EXIT LOCATIONS ARE SHOWN IN THE
 CORRECT LOCATION. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1C) UNDER THE LIFE SAFETY NOTES THERE IS A STATEMENT
 THAT ALL INTERIOR FINISHES TO COMPLY WITH THE FFPC 101
 6TH EDITION 10.2.2 AND CHAPTER 10 FOR MERCANTILE
 OCCUPANCY. PLEASE NOTE UNDER THE 2017 FBC-B 6TH EDITION
 TABLE803.11 PROVIDES THE REQUIREMENTS BY OCCUPANCY
 PLEASE LIST THE FLAME SPREAD AND SMOKE DEVELOPMENT BY
 CLASS FOR EITHER A SPRINKLERED OR NON-SPRINKLERED
 BUILDING.
  
 2) SHEET A101 SHOWS VARIOUS DETAIL MARKERS FOR SHEET
 A300 AND A301 BUT THE DRAWING INDEX DOES NOT SHOW THESE
 SHEETS EXIST, NOR DOES THE PLANS SHOW THESE VARIOUS
 ELEVATION VIEWS. CODE COMPLIANCE CANNOT BE ACHIEVED
 WITHOUT THESE DETAILS. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 3) SHEET A501, A502 & A503 ALL SHOW VARIOUS COUNTERS
 WITH THE COUNTER TOP AT A HEIGHT OF 36 INCHES ABOVE THE
 FINISH FLOOR. PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY
 CODE SECTIONS:
  
 CHECK WRITING SURFACES. 904.3.3. CHECK WRITING
 SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL
 COMPLY WITH 902.3.
  
 WORK SURFACES. 902.3 HEIGHT. THE TOPS OF WORK SURFACES
 SHALL BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 4) SHEET A101 IN THE BREAK ROOM AREA LABELED ROOM 106
 THE PLANS SHOW A DETAIL MARKER 1/ A301. THIS SHEET DOES
 NOT EXIST, PLEASE SHOW COMPLIANCE WITH THE REQUIREMENTS
 OF THE 2017 FBC-ACCESSIBILITY CODE SECTIONS SEE BELOW.
  
 SHEET A-201 BREAK ROOM COUNTER AND SINK PLEASE CHECK
 YOUR VERTICAL MEASUREMENTS TO THE COUNTER TOP.
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. SINKS
 SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE
 RIM OR COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
 WORK SURFACES. 902.3 HEIGHT. THE TOPS OF WORK SURFACES
 SHALL BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 5) SHEET A-201 DETAILS 4 & 5 BOTH ARE OF THE RESTROOM
 ELEVATIONS DEPICTING THE GRAB BARS. ONE HAS THE GRAB
 BAR AT A HEIGHT OF 2 FEET 9 INCHES WHILE THE OTHER IS 2
 FEET 10 INCHES TO THE CENTER LINE OF THE GRAB BAR.
 PLEASE NOTE CHANGES TO THE 2017 ACCESSIBILITY CODE:
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 6) SHEET A-201 DETAIL 5 THE TOILET PAPER DISPENSER
 LOCATION IS TAKEN FROM THE BACK WALL TO THE CENTERLINE
 OF THE DISPENSER CLOSET TO THE WATER CLOSET. PLEASE
 REVIEW 2017 FBC-ACCESS. CODE 604.7 DISPENSERS. TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  