2020-02-04 08:56:03GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE A DRAWING OR SURVEY SHOWING THE
 GENERATOR LOCATION FBC 107
 2) PLEASE PROVIDE SIGNED AND SEALED STRUCTURAL DETAIL
 FROM AN ARCHITECT OR ENGINEER SHOWING THE GENERATOR
 ATTACHMENT TO A FOUNDATION TO COMPLY WITH THE WIND
 LOADS PER FBC 1609.1
 3 PLEASE SHOW THE WIND DESIGN PARAMETERS USED (CODE
 VERSION, WIND SPEEDS ETC). FBC 1603.1.4
 4) PLEASE PROVIDE SIGNED AND SEALED FOUNDATION DETAILS
 IF NEEDED.
 5) PLEASE STATE ON THE LOCATION DRAWING THAT THE
 GENERATOR ELEVATION WILL COMPLY WITH FLOOD ELEVATION
 PER FBC 1612.4