| Date |
Text |
| 2020-06-24 15:46:33 | PLAN REVIEW - ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 3RD REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | COMMENTS FROM 2ND ELECTRICAL REVIEW HAVE NOT BEEN |
| | ADDRESSED. BELOW IS A COPY FOR YOUR REFERENCE. |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED - DENIED |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. SHEET E-2.0, NOTE 14, THE NEC AND FBC SPECIFIED FOR |
| | DESIGN IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC |
| | PREFACE (ALSO SEE CURRENT CODES ABOVE)(2ND REVIEW: NOT |
| | CORRECTED.) |
| | 2. SEVERAL NOTES THROUGHOUT INDICATE AFCI PROTECTION |
| | THAT IS NOT CODE COMPLIANT. REMOVE AND/OR EDIT NOTES TO |
| | REFLECT CURRENT CODE COMPLIANCE. ALL BRANCH CIRCUITS |
| | THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING |
| | ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8, 210.12; FBC RE E3902 (2ND REVIEW: NOT |
| | CORRECTED.) |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 (I SEE THAT A SEPARATE SHEET IS INCLUDED |
| | WITH THIS INFORMATION, BUT IT IS NOT SHOWN ON THE |
| | SIGNED/SEALED PLANS. PROVIDE CORRECTION.) |
| | 4. CORRECTED. |
| | 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 (2ND |
| | REVIEW: NOT CORRECTED.) |
| | 6. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS BASED ON THE METHOD PRESCRIBED IN FBC |
| | RESIDENTIAL. NEC 220; FBC RE E3602.2 (2ND REVIEW: NOT |
| | CORRECTED, ALL LOADS NOT INCLUDED.) |
| | 7. RISER DIAGRAM PROVIDED, BUT NEEDS CORRECTIONS. SEE |
| | NOTES BELOW. |
| | 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER AT THE PANEL FOR THE SUB-PANEL IN MAIN |
| | HOUSE. NEC 225.31, 225.32 (2ND REVIEW: NOT CORRECTED.) |
| | 9. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| | CIRCUIT. NEC 250.32; FBC RE3607.3 (2ND REVIEW: NOT |
| | CORRECTED.) |
| | 10. CORRECTED. |
| | NEW COMMENTS: |
| | 11. RISER DIAGRAM SHOWS A METER MAIN COMBO WITH FEED |
| | THROUGH LUGS, AND THEN A SEPARATE DISCONNECT NEXT TO |
| | THIS METER MAIN. WHAT IS THE PURPOSE OF THIS |
| | DISCONNECT? ADDITIONALLY, THE WIRE SIZE TO THIS |
| | DISCONNECT IS SHOWN AS 1/0, WHICH IS NOT RATED FOR 200 |
| | AMPS. PROVIDE CORRECTION. NEC 310.15(B)(7) AND (B)(16); |
| | FBC RE E3603.1, E3705.1; WPB FBC 107.2.1 |
| | 12. WIRE SIZE TO PANEL A IS NOT SIZED CORRECTLY. BASED |
| | ON THE 200 AMP OVERCURRENT PROTECTION SHOWN, THESE |
| | CONDUCTORS SHOULD BE SIZED FOR 200 AMPS. PROVIDE |
| | CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC RE |
| | E3603.1, E3705.1 |
| | END OF COMMENTS. |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | SINCERELY, |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |
| | |