2020-06-24 15:05:02PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES.
 ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 2ND REVIEW
  
  
 ****IMPORTANT:
 ENERGY CALCULATIONS NEED TO BE SIGNED BY THE OWNER
 PRIOR TO ISSUING THE PERMIT.
  
 1- CORRECTED
  
 2- CORRECTED
  
 3- CORRECTED
  
 4- IMPACT FEE. (SEE IMPACT FEE REVIEW)
  
  
 5- DESIGNER SHALL SELECT MODEL OF EXTERIOR DOORS TO BE
 INSTALLED. (NOT ADDRESSED)
  
 DESIGNER SHALL REVIEW AND APPROVE PRODUCT APPROVALS.
 (NOT ADDRESSED)
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 A) METAL ROOFING. (NOT ADDRESSED)
  
 B) ROOFING TILES.(NOT ADDRESSED)
  
 C) GARAGE OVERHEAD DOOR DOOR. NEED TO PROVIDE PRODUCT
 APPROVAL FOR DOOR THAT MEETS THE DESIGN PRESSURE
 CALCULATED BY THE ARCHITECT OF RECORD ON SHEET A-2.0.
 (NOT ADDRESSED)
  
 D) NEED PRODUCT APPROVAL FOR ARCHED ENTRY DOOR AS SHOWN
 ON PLANS. (NOT ADDRESSED)
  
 E) NEED PRODUCT APPROVAL FOR FLAT ROOF AT THE PORTE
 COCHERE. (NOT ADDRESSED)
  
 NEW COMMENTS:
  
 6- SPECIFIED FOOTING SIZE WF5 -20 DOESN'T COMPLY WITH
 THE MINIMUM FOOTING DEPTH REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL. REVISE FOOTING SIZE AS REQUIRED. NOTE:
 REVISE TYPICAL WALL SECTION ON SHEET A-3.0 ALSO. KEEP
 IN MIND THAT NEED TO PROVIDE THE 6" CLEARANCE FOR
 TERMITE INSPECTION. (NOT ADDRESSED)
  
 7- TYPE OF DOOR SHOWN ON THE DOOR TYPES ON SHEET A-1.0
 DOESN'T MATCH TYPE OF DOOR SHOWN ON THE EXTERIOR
 ELEVATION. EXTERIOR ELEVATION SHOWS AN ARCHED DOOR.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS. PRODUCT APPROVAL REQUIRED FOR ARCHED DOOR.
 (NOT ADDRESSED)
  
 8- ENERGY CALCULATIONS SUBMITTED: (NOT ADDRESSED)
  
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION.
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING COMPLETE ADDRESS, OWNER'S INFORMATION, THE
 BUILDER'S NAME, PERMIT OFFICE AND JURISDICTION
 (604700). SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
 C) THE AREA WEIGHTED AVERAGE SHGC SHOWN ON ITEM #7 ON
 PAGE 1 DOESN'T COMPLY WITH THE MAXIMUM FENESTRATION
 SHGC REQUIRED BY SEC. R405.5.3.4 OF FBC-ENERGY
 CONSERVATION. THE MAXIMUM AREA WEIGHTED AVERAGE
 FENESTRATION SHGC ALLOWED IS 0.50. ENERGY CALCULATIONS
 SUBMITTED SHOW 0.754. REVISE AS REQUIRED TO COMPLY.
  
 D) FLOOR TYPE SHOWN ON ITEM #8 ON PAGE 1 IS INCORRECT
 AND IT DOESN'T MATCH FLOOR PLANS. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. (NOT
 ADDRESSED)
  
 E)REVISE ITEM #9(A) TO MATCH PLANS. INSULATION R-VALUE
 DOESN'T MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. (NOT
 ADDRESSED)
  
 F) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 5.
 TYPICALLY, THE RATIO IS 1/150 NOT 1/300. SEC. R806.2
 FBC-RESIDENTIAL. OR PERSON PREPARING THE ENERGY
 CALCULATIONS TO PROVIDE COMPLETE DETAILS/SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE 1/300 RATIO AS REQUIRED BY
 THE EXCEPTION ON SEC. R806.2. NOTE: ARCHITECT OF RECORD
 NEEDS TO REVIEW/APPROVE THEM PRIOR TO SUBMITTAL. (NOT
 ADDRESSED)
  
 G) REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. (NOT
 ADDRESSED)
  
 9- ARCHITECTURAL PLANS SHOW CEILING FANS AND THE ENERGY
 CALCULATIONS ARE TAKING THE CREDIT FOR THEM. NEED TO
 SPECIFY THE CEILING FAN SIZE ON EACH ROOM SHOWING
 COMPLIANCE WITH TABLE R405.7.6 FBC-ENERGY CONSERVATION.
 (NOT ADDRESSED)
  
 10- CORRECTED
  
 11- PROPOSED FLOOR PLAN ON SHEET A-1.0 SHOWS 3'-0"
 MASONRY OPENING FOR THE ENTRY DOOR. THIS MASONRY
 OPENING DIMENSION IS INCORRECT FOR THE REQUIRED 3'-0"
 DOOR. REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
 (NOT CORRECTED)
  
 12- PROVIDE STRUCTURAL BUCK DETAIL AND SPECIFICATIONS
 FOR NEW OVERHEAD GARAGE DOOR. SEC. R301.1
 FBC-RESIDENTIAL. (NOT CORRECTED)
  
 13- NEW PORTE COCHERE: (NOT ADDRESSED)
 A) ROOF FRAMING PLAN ON SHEET S-2.0: PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR THE FASTENING OF THE
 2X10 ROOF JOISTS. PROVIDE COMPLETE DETAILS/SPECS FOR
 THE WOOD LEDGER, FASTENERS, ETC. SEC. R301.2.1
 FBC-RESIDENTIAL.
 NOTE: THERE IS NOT METAL ROOFING ON A FLAT ROOF. REVISE
 ROOF SPECS.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE ROOF DRAINAGE INCLUDING EMERGENCY
 SCUPPERS. SEC. R903.4 FBC-RESIDENTIAL. (NOT ADDRESSED)
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
  