| Plan Review Notes For Permit 19111096 |
| Permit Number |
19111096 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-03-30 13:26:34 | ROOFING REVIEW: | | | | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL) | | | | | | A) METAL ROOFING. FLORIDA PRODUCT APPROVAL FL21082-R2 | | | WAS SUBMITTED WITH INFORMATION FOR CONCRETE TILE AND IS | | | MISSING THE INFORMATION FOR THE METAL ROOF. PROVIDE | | | COMPLETE INSTALLATION INSTRUCTIONS FOR THE METAL ROOF. | | | | | | B) ROOFING TILES. FLORIDA PRODUCT APPROVAL FL7849-R11 | | | SUBMITTED IS INCOMPLETE. PROVIDE COMPLETE INSTALLATION | | | INSTRUCTIONS AND CLEARLY MARK FASTENING METHOD. NOTE: | | | SEE PLANS FOR LOCATION OF PROPOSED INSTALLATION. | | | ADDITIONAL PRODUCT APPROVALS MAY BE REQUIRED BASED ON | | | THE PROPOSED INSTALLATION METHOD. SEE ARCHITECT'S | | | EXTERIOR ELEVATIONS. | | | | | | C) FLAT ROOF FOR THE PORTE COCHERE. AND, CLEARLY MARK | | | WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO | | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | R301.1 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY | | | DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, | | | THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE | | | REQUIRED. |
|