Plan Review Notes
Plan Review Notes For Permit 19111096
Permit Number 19111096
Review Stop E
Sequence Number 2
Notes
Date Text
2020-03-20 09:40:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. SHEET E-2.0, NOTE 14, THE NEC AND FBC SPECIFIED FOR
 DESIGN IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)(2ND REVIEW: NOT
 CORRECTED.)
 2. SEVERAL NOTES THROUGHOUT INDICATE AFCI PROTECTION
 THAT IS NOT CODE COMPLIANT. REMOVE AND/OR EDIT NOTES TO
 REFLECT CURRENT CODE COMPLIANCE. ALL BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902 (2ND REVIEW: NOT
 CORRECTED.)
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3 (I SEE THAT A SEPARATE SHEET IS INCLUDED
 WITH THIS INFORMATION, BUT IT IS NOT SHOWN ON THE
 SIGNED/SEALED PLANS. PROVIDE CORRECTION.)
 4. CORRECTED.
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 (2ND
 REVIEW: NOT CORRECTED.)
 6. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS BASED ON THE METHOD PRESCRIBED IN FBC
 RESIDENTIAL. NEC 220; FBC RE E3602.2 (2ND REVIEW: NOT
 CORRECTED, ALL LOADS NOT INCLUDED.)
 7. RISER DIAGRAM PROVIDED, BUT NEEDS CORRECTIONS. SEE
 NOTES BELOW.
 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR THE SUB-PANEL IN MAIN
 HOUSE. NEC 225.31, 225.32 (2ND REVIEW: NOT CORRECTED.)
 9. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3 (2ND REVIEW: NOT
 CORRECTED.)
 10. CORRECTED.
  
 NEW COMMENTS:
  
 11. RISER DIAGRAM SHOWS A METER MAIN COMBO WITH FEED
 THROUGH LUGS, AND THEN A SEPARATE DISCONNECT NEXT TO
 THIS METER MAIN. WHAT IS THE PURPOSE OF THIS
 DISCONNECT? ADDITIONALLY, THE WIRE SIZE TO THIS
 DISCONNECT IS SHOWN AS 1/0, WHICH IS NOT RATED FOR 200
 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(7) AND (B)(16);
 FBC RE E3603.1, E3705.1; WPB FBC 107.2.1
 12. WIRE SIZE TO PANEL A IS NOT SIZED CORRECTLY. BASED
 ON THE 200 AMP OVERCURRENT PROTECTION SHOWN, THESE
 CONDUCTORS SHOULD BE SIZED FOR 200 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC RE
 E3603.1, E3705.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  