| 2019-12-06 16:07:21 | 11/06/2019 1ST PLUMBING/ REVIEW **DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLUMBING SANITARY RISER HAS SHOWER AND LAV NOT |
| | VENTED CORRECTLY, SHOW LAV OFF VENT BETWEEN WATER |
| | CLOSET AND SHOWER OR IN A DOUBLE WYE PATTERN STRAIGHT |
| | TO WC AND USE ONE SIDE FOR LAV AND THE OTHER FOR SHOWER |
| | THAT WAY TRAP SEAL ARE PER 2017 FBC SEC. R3201.2.1 TRAP |
| | SEAL PROTECTION. |
| | 2. LAV IN MASTER ON AAV NOT SHOWN ON ISOMETRIC DRAWING |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 3. WASHING MACHINE NOT VENTED OR P-TRAP SHOWN ON |
| | ISOMETRIC DRAWING NEED AAV OR VTR PER THE 2017 FBC SEC. |
| | R3201.2.1 TRAP SEAL PROTECTION/. |
| | 4. KITCHEN DRAIN SHOWN AS AN 1 1/2" BUT IN MOST CASES A |
| | 2 " LINE WORK BETTER FOR GREASE STOPPAGE REASON, NOT |
| | REQUIRED BUT RECOMMEND. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |