| 2019-11-22 16:02:13 | 11/22/2019 1ST GAS REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT |
| | WILL BE DONE AT FIELD, IF NOT TO CODE, IT MAY NEED TO |
| | BE BOUT UP TO CODE COMPLIANCE. |
| | 2. PLEASE LABEL SHUTOFF VALVES, UNIONS, DRIP LEGS, |
| | BTU'S OF GENERATOR AND REGULATORS (IF NEEDED) ON |
| | ISOMETRIC PER THE 2017 FBC RES. SEC. G2401.1.3. |
| | 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| | 4. SUBMIT COPIES OF THE CORRECT SIZING TABLE USED IN |
| | THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH |
| | SETS OF PLANS LISTING THE SIZING TABLES FROM GAS CODES |
| | OR ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF |
| | THIS SYSTEM PER THE 2017 FBC RES. SEC. G2413.3. |
| | 5. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC RES. SEC. G2413.2. |
| | 7. THE CITY RECORDS INDICATE AN EXISTING GAS METER. THE |
| | BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO |
| | THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| | PER THE 2017 FBC RES. SECS. G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.3. |
| | 8. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1 |
| | GENERAL. |
| | 9. PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR AND THEY SHALL BE ONSITE FOR FINAL GAS |
| | INSPECTION. THE GENERATOR SHALL BE LISTED AND APPROVED. |
| | NFPA 58 SEC. 5.20.1. THE GENERATOR SHALL MEET THE |
| | REQUIREMENTS OF UL 2200. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |