Plan Review Notes
Plan Review Notes For Permit 19111031
Permit Number 19111031
Review Stop M
Sequence Number 1
Notes
Date Text
2019-11-21 10:56:271ST REVIEW FBC-2017 MECHANICAL
 SUBMITTAL #19111031
 MASTER PERMIT #17121030
 11/21/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DUE TO THE FACT THAT THERE IS UNCOMPLETED MECHANICAL
 WORK ASSOCIATED WITH THE BREWERY THE COMMISSIONING
 REPORT IS NOT ACCEPTED AT THIS TIME. PLEASE SEE PAGE 1
 OF THE REPORT WHICH VERIFIES THAT ALL ITEMS AND
 EQUIPMENT HAVE BEEN INSTALLED ACCORDING TO THE
 CONSTRUCTION DOCUMENTS INSPECTION. THAT CLAIM APPEARS
 TO BE INACCURATE BASED ON WPB BUILDING DEPARTMENT
 INSPECTION RECORDS WHICH INDICATE THE TWO GAS VENTS FOR
 THE BREWHOUSE AND HOT LIQUOR TANK (TANKS 12 & 13) ARE
 INCOMPLETE AND NOT INSTALLED PER THE APPROVED
 MECHANICAL PLAN AND ENGINEERED SPECIFICATIONS. FURTHER,
 THE STRUCTURAL ENGINEERING FOR INSTALLATION OF THE
 EXTERIOR GLYCOL CHILLER SUPPORT BASE UNDER PERMIT
 #19090515 HAS FAILED BOTH BUILDING AND MECHANICAL
 REVIEWS, AND CORRECTED PLANS HAVE NOT BEEN RESUBMITTED
 TO DATE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved