Plan Review Notes
Plan Review Notes For Permit 19111029
Permit Number 19111029
Review Stop P
Sequence Number 1
Notes
Date Text
2019-12-05 10:13:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 19111029 831 BELVEDERE RD
 MP #18030198
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 NOTE: AN IRRIGATION PLAN HAS NOT BEEN INCLUDED IN THIS
 SUBMITTAL PACKAGE. AN IRRIGATION PLAN REVIEW HAS NOT
 BEEN PERFORMED AT THIS TIME. A SEPARATE IRRIGATION
 PERMIT AND PLANS WILL BE REQUIRED FOR A CONTRACTOR TO
 PERFORM THE RELATED WORK. PROVIDE COMPLETE PLANS AND
 DOCUMENTS, REFLECTING EQUIPMENT SPECIFICATIONS, LAYOUT
 AND DISTRIBUTION PER WPB FBC 107.2.1.
  
 1. TO BE CLEAR, THE KITCHEN SINK, NOT JUST THE LAVATORY
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 ACCESSIBILITY CODE 2017 6TH EDITION. PER WPB FBC
 107.2.1 AND 107.3.5.1.3, CLEARLY SHOW COMPLIANCE WITH
 THE FOLLOWING.
 A) PER FBC ACC 212.3, WHERE SINKS ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE
 PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY
 WITH 606.
 B) PER FBC ACC 606.2 AS PERMITTED BY EXCEPTION 1,
 PROVIDE A PARALLEL APPROACH COMPLYING WITH 305 TO THE
 KITCHEN SINK; CENTER THE SINK ON THE 30 INCH BY 48 INCH
 CLEAR SPACE.
 C) PER FBC ACC 606.3, SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 2. RE: PLAN SHEET A6; TOILET FIXTURE SPECIFICATIONS
 A) ITEM 1: TILT MIRROR; BOTTOM EDGE OF THE REFLECTING
 SURFACE SHALL NOT EXCEED 40 INCHES A.F.F PER FBC ACC
 603.3.
 B) ITEM 2: GRAB BARS; GRAB BAR HEIGHT: GRAB BARS SHALL
 BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840
 MM) MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE PER FBC ACC 609.4
 C) ITEM 8: PER WPB FBC 107.2.1 AND 107.3.5.1.3, REMOVE
 REFERENCE TO DRINKING FOUNTAIN AS THERE ARE NONE SHOWN
 ON THE PLAN.
  
 3. RE: PLAN SHEET A6; DETAIL B. PER WPB FBC 107.2.1 AND
 107.3.5.1.3, CLEARLY SHOW THE FOLLOWING.
 A) PER FBC ACC 604.2, THE CENTERLINE OF THE WATER
 CLOSET SHALL BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM
 FROM THE SIDE WALL OR PARTITION.
 B) PER FBC 604.5.2, THE REAR WALL GRAB BAR SHALL BE 36
 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
  
 4. RE: PLAN SHEET P1; TANKLESS WATER HEATER. PER WPB
 FBC 107.2.1 AND 107.3.5.1.3, PROVIDE THE FOLLOWING.
 A) LOCATION OF THE UNIT
 B) FULL SIZED AND ACCESSIBLE SHUT OFF VALVE PER FBC PL
 503.1 AND 606.1( 8)
 C) EQUIPMENT SCHEDULE AND MANUFACTURER?S SPECIFICATION
 SHEET INDICATING MANUFACTURER AND MODEL #, ELECTRICAL
 CHARACTERISTICS, MOUNTING DETAILS AND GPM. CONFIRM THAT
 IT WILL MEET THE FIXTURE DEMAND IN ACCORDANCE WITH FBC
 PL 603 AND 604.
  
 5. RE: PLAN SHEET P1; TEMPERED WATER. PER FBC PL 416.5,
 THE WATER TEMPERATURE LIMITING DEVICE SHALL CONFORM TO
 ASSE 1070 AND ADDITIONALLY AS REQUIRED BY FBC PL
 607.1.2, SHALL LIMIT THE TEMPERED WATER TO A MAXIMUM OF
 110?F. PER WPB FBC 107.2.1 AND 107.3.5.1.3, INDICATE
 THE SAME.
  
 6. RE: PLAN SHEET P1; EXISTING WATER SUPPLY. PER WPB
 FBC 107.2.1 AND 107.3.5.1.3, INDICATE THE SIZE OF THE
 EXISTING WATER SUPPLY LINE AND SHOW IT IN REGARD TO
 SERVICING THE ADJACENT EXISTING DRY CLEANING FACILITY.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19111029 831 BELVEDERE RD
 MP #18030198
  