| 2019-12-06 12:48:12 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19111029 |
| | 12/6/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1: THE MINIMUM ROOF GUARD HEIGHT SHALL BE 42" |
| | FROM THE FINISHED ROOF SURFACE- PLEASE CORRECT PER |
| | SECTION 304.11 FBC M. |
| | |
| | 2) M1: SHOW THE LOCATION OF THE O/A INLET WITH REQUIRED |
| | CLEARANCES- SECTION 401.4 FBC M. |
| | |
| | 3) M1: MIAMI-DADE NOA #14-1224.10 FOR THE AC STAND IS |
| | OUTDATED AND EXPIRED. PLEASE CORRECT THE NOTE TO |
| | INDICATE THE CURRENT NOA #17-0320.02 AND SUBMIT TWO |
| | COPIES OF THE DOCUMENT. |
| | |
| | 4) M1: SHOW THE BATH EXHAUST DUCT RUN AND TERMINATION |
| | LOCATION- SECTION 501.1.3.1 FBC M. |
| | |
| | 5) THE AC AND ENERGY CALCULATIONS WERE NOT RESUBMITTED- |
| | PLEASE PROVIDE THE DOCUMENTS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |