2019-12-17 08:19:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS FROM AUBMISSION 18030198 THAT HAVE
 BEEN ADDRESSED SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES.
 ANY NEW COMMENTS WILL BE LISTED AFTER PREVIOUS
 COMMENTS.
  
 1. ONLY ONE SERVICE PER ADDRESS IS PERMITTED. PROVIDE
 CORRECTION. WPB FBC 107.2.1; NEC 230.2 (NOT CORRECTED.
 THE ADDITIONAL SERVICE IS NOT DEPENDENT ON FPL
 APPROVAL. PER 230.2, ADDITIONAL SERVICES ARE ONLY
 PERMITTED WHEN THE EXCEPTIONS TO THIS CODE ARE MET.
 RESPONSE DOES NOT INDICATE COMPLIANCE. ADDITIONAL METER
 CANS ARE PERMITTED FOR SEPARATE TENANT SPACES IF
 DESIRED, BUT ONLY ONE SERVICE. SEE NEC 230.2. PROVIDE
 CORRECTION.)
 2. PROVIDE ACCURATE RISER DIAGRAM. RISER PROVIDED ONLY
 SHOWS EXISTING SERVICE. NEC 215.5, 230, 250.50, 250.94,
 408.30 (RISER PROVIDED, BUT NOT APPROVED AS IS.)
 3. CORRECTED.
 4. CORRECTED.
 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9 (AIC RATING OF PANEL NOT PROVIDED.)
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10 (NOT PROVIDED.)
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
  
 NEW COMMENT:
  
 13. FEEDERS TO PANEL A AND B NOW SHOW A REDUCED
 NEUTRAL, SIZED 1/0. IF A REDUCED NEUTRAL IS TO BE USED,
 A DEMAND LOAD FOR THE NEUTRAL IS REQUIRED. PROVIDE
 CORRECTION. NEC 220.61
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved