| Plan Review Notes For Permit 19110913 |
| Permit Number |
19110913 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-21 10:35:59 | CONVENTIONAL SHORING AND RESHORING PLANS, BUILDING | | | REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- PLANS SUBMITTED ARE COPIES. NEED TO PROVIDE PLANS | | | WITH ORIGINAL DIGITAL SIGNATURE AS REQUIRED BY CHAPTER | | | 471 F.S. | | | NOTE: DRAWINGS NEED TO BE ON THE RIGHT ORIENTATION TO | | | BE OPENED AND READ WITHOUT HAVING TO ROTATE EACH | | | DRAWING. | | | | | | 2- INFORMATION SUBMITTED IS NOT PROPERLY DOWNLOADED. IF | | | SUBMITTING DRAWINGS, THEN THEY NEED TO BE UPLOADED | | | INDIVIDUALLY IN THE DRAWING FILE. OR IF YOU PREFER TO | | | DOWNLOAD FILE IN THE SUPPORTING DOCUMENTS, THEN ALL | | | DRAWINGS NEED TO BE SUBMITTED ON THE RIGHT ORIENTATION | | | TO BE READ WITHOUT HAVING TO ROTATE EACH DRAWING. | | | PLEASE COORDINATE WITH LIBRARIAN FOR PROPER DOWNLOADING | | | PROCEDURE. SEC. 107.2.1.2 CITY AMENDMENTS. | | | NOTE: PLEASE MAKE SURE ALL SUBMITTED DRAWINGS ARE THE | | | ONES REVIEWED/APPROVED BY THE ENGINEER OF RECORD. | | | | | | 3- IT LOOKS LIKE THE SHORING AND RESHORING DRAWINGS ARE | | | NOT FOR ALL FLOORS. CLEARLY SPECIFY ON THE SUBMITTAL | | | FORM WHAT FLOORS ARE COVERED IN THIS SUBMITTAL. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|