Plan Review Notes
Plan Review Notes For Permit 19110910
Permit Number 19110910
Review Stop P
Sequence Number 4
Notes
Date Text
2020-02-07 15:13:20 
 PLUMBING PROVISO
  
 1. ON THE WATER ISOMETRIC IT STATES THE T+P TO EXTERIOR
 THE T+P LINE SHALL TERMINATE WITH IN AIR GAP IN THE
 SAME ROOM AS THE WATER HEATER. PER FBC PL 504.6(2)
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. A NOTE ON THE PLAN
 WILL SUFFICE. PER FBC PL 416.5
  
 6. ON THE SITE CIVIL PLAN IT SHOWS A DUAL CHECK VALVE
 ON THE WATER SERVICE METER A RPZ BACKFLOW DEVICE IS
 REQUIRED PER WPB UTILITIES CROSS CONNECTION MANUAL
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW. PLACE
 NOTE ON THE PLAN
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]