Plan Review Notes
Plan Review Notes For Permit 19110910
Permit Number 19110910
Review Stop P
Sequence Number 3
Notes
Date Text
2020-01-28 12:23:523RD REVIEW:19120803
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: NO RESPONSE LETTER WAS PROVIDED FOR
 PREVIOUS COMMENTS IT WAS UNCLEAR HOW ALL THE COMMENTS
 WERE ANSWERED.
  
 1. ON THE WATER ISOMETRIC IT STATES THE T+P TO EXTERIOR
 THE T+P LINE SHALL TERMINATE WITH IN AIR GAP IN THE
 SAME ROOM AS THE WATER HEATER. PER FBC PL 504.6(2)
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. A NOTE ON THE PLAN
 WILL SUFFICE. PER FBC PL 416.5
  
 3. PLEASE IDENTIFY THE THERMAL EXPANSION DEVICE IT CAN
 NOT BE APPROVED UNTIL IT IS IDENTIFIED PROVIDE
 MANUFACTURE SPECIFICATIONS FOR A VALVE OR MODEL NUMBER
 OF A TANK. PER FBC PL 607.3
  
 4. THE EYE WASH IS NOT VENTED PLEASE PROVIDE A VENT PER
 FBC PL 901.2.1
  
 5. SHT. P1 NOTE ON H.C. RESTROOM PLAN LAYOUT STATES
 GRAB BARS TO BE MEASURED TO THE CENTERLINE THEY SHALL
 BE MEASURED TO THE TOP OF THE GRIPPING SURFACE. PER FBC
 ACC 609.4
  
 6. ON THE SITE CIVIL PLAN IT SHOWS A DUAL CHECK VALVE
 ON THE WATER SERVICE METER A RPZ BACKFLOW DEVICE IS
 REQUIRED PER WPB UTILITIES CROSS CONNECTION MANUAL
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW. PLACE
 NOTE ON THE PLAN
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]