| 2020-01-28 12:23:52 | 3RD REVIEW:19120803 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: NO RESPONSE LETTER WAS PROVIDED FOR |
| | PREVIOUS COMMENTS IT WAS UNCLEAR HOW ALL THE COMMENTS |
| | WERE ANSWERED. |
| | |
| | 1. ON THE WATER ISOMETRIC IT STATES THE T+P TO EXTERIOR |
| | THE T+P LINE SHALL TERMINATE WITH IN AIR GAP IN THE |
| | SAME ROOM AS THE WATER HEATER. PER FBC PL 504.6(2) |
| | |
| | 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. A NOTE ON THE PLAN |
| | WILL SUFFICE. PER FBC PL 416.5 |
| | |
| | 3. PLEASE IDENTIFY THE THERMAL EXPANSION DEVICE IT CAN |
| | NOT BE APPROVED UNTIL IT IS IDENTIFIED PROVIDE |
| | MANUFACTURE SPECIFICATIONS FOR A VALVE OR MODEL NUMBER |
| | OF A TANK. PER FBC PL 607.3 |
| | |
| | 4. THE EYE WASH IS NOT VENTED PLEASE PROVIDE A VENT PER |
| | FBC PL 901.2.1 |
| | |
| | 5. SHT. P1 NOTE ON H.C. RESTROOM PLAN LAYOUT STATES |
| | GRAB BARS TO BE MEASURED TO THE CENTERLINE THEY SHALL |
| | BE MEASURED TO THE TOP OF THE GRIPPING SURFACE. PER FBC |
| | ACC 609.4 |
| | |
| | 6. ON THE SITE CIVIL PLAN IT SHOWS A DUAL CHECK VALVE |
| | ON THE WATER SERVICE METER A RPZ BACKFLOW DEVICE IS |
| | REQUIRED PER WPB UTILITIES CROSS CONNECTION MANUAL |
| | A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW. PLACE |
| | NOTE ON THE PLAN |
| | |
| | END OF COMMENTS |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |