Plan Review Notes
Plan Review Notes For Permit 19110910
Permit Number 19110910
Review Stop M
Sequence Number 3
Notes
Date Text
2020-01-28 11:36:453RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19110910
 1/28/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 (COMMENTS #1, 2, 4, 5 & 6 LISTED BELOW ARE REMAINING
 FROM THE 1ST AND 2ND REVIEW.)
  
 1) THE ENGINEER OF RECORD RESPONSIBLE FOR THE DESIGN
 SHALL PROVIDE AN APPROVAL STAMP ON THE SUBMITTED
 ENERGYGAUGE COMPLIANCE REPORT- SEE SECTION C103.1.1.2
 FBC EC. (THE EOR SHALL ALSO PROVIDE AN APPROVAL STAMP
 ON THE HVAC CALCULATIONS).
  
 2) THE WIND FORCE CALCULATIONS SHALL BE ELECTRONICALLY
 SIGNED AND SEALED BY THE ENGINEER- FL. STATUTE 471.025
 AND SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
  
 4) M1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE THE
 SUPPLY AIR SYSTEMS OF AHU'S 1, 2, 3, 4, 5, 6, & 7-
 SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION
 FOR THE DETECTORS IN THE SUPPLY CAN BE APPLIED IF THE
 MANUFACTURER'S PERFORMANCE DATA INDICATES THE AIR
 HANDLERS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR.
 (THE EOR RESPONSE NARRATIVE INDICATES AREA SMOKE
 DETECTORS PROVIDED IN LIEU OF REQUIRED DS DETECTORS IN
 THE SUPPLY SYSTEMS. PLEASE REVIEW THE SUBMITTED FA
 PLANS SHOWING 9 DS DETECTORS IN THE RETURNS, AND ONLY 3
 AREA SMOKE DETECTORS FOR THE ENTIRE OCCUPANCY. PLEASE
 SEE DS DETECTOR NOTE ON SHEET M2).
  
 5) M1 & M2: IT APPEARS THAT VEHICLES WILL EITHER DRIVE
 INTO OR BE STORED IN THE "PROPOSED LOADING" AREA WHERE
 THE LARGE BAY DOORS ARE. PROVIDE AN EXHAUST VENTILATION
 SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1 AND SECTION
 404.1 FBC M.
 (SHEET M1 & M2: INDICATE SEQUENCE OF OPERATION FOR THE
 EXHAUST VENTILATION SYSTEM- REFER TO SECTION 404.1 FBC
 M).
  
 6) M1: PLEASE PLACE A NOTE ON THE PLAN INDICATING THAT
 THE EMERGENCY GENERATOR WILL BE INSTALLED UNDER A
 SEPARATE PERMIT- SECTION 107.2.1 FBC M.
  
 NEW COMMENT:
  
 1) THE HVAC CALCULATIONS INDICATE 48 KW OF HEAT
 REQUIRED IN THE MAIN WAREHOUSE AND 5KW IN THE SECURE
 STORAGE AREA. ACCORDING TO THE AC EQUIPMENT SCHEDULE
 THERE WILL BE A SHORTAGE OF 8KW IN THE WAREHOUSE AND
 5KW IN THE STORAGE AREA- SECTION C403.2.1 FBC EC.
  
 2) ADVISORY: THE REQUIRED SENSORS FOR THE LOADING DOCK
 EXHAUST SYSTEM, AND THE SHOP DRAWINGS FOR THE CONDENSER
 SERVICE PLATFORMS AND GUARDRAILS MAY BE DEFERRED
 SUBMITTALS. PLEASE NOTE THAT EACH SUBMITTAL SHALL BEAR
 THE APPROVAL STAMP OF THE EOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  