Plan Review Notes
Plan Review Notes For Permit 19110910
Permit Number 19110910
Review Stop M
Sequence Number 2
Notes
Date Text
2020-01-13 13:19:452ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19110910
 1/13/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER OF RECORD RESPONSIBLE FOR THE DESIGN
 SHALL PROVIDE AN APPROVAL STAMP ON THE SUBMITTED
 ENERGYGAUGE COMPLIANCE REPORT- SEE SECTION C103.1.1.2
 FBC EC.
  
 2) THE WIND FORCE CALCULATIONS SHALL BE ELECTRONICALLY
 SIGNED AND SEALED BY THE ENGINEER- FL. STATUTE 471.025
 AND SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
  
 3) SHEETS M1 & M2: THE O/A CALCULATIONS ARE INDICATING
 MECHANICAL VENTILATION WILL BE PROVIDED FOR THE THE NEW
 WORK SHOP HOWEVER NO MECHANICAL VENTILATION IS SHOWN ON
 THE PLAN. PLEASE NOTE THAT THE MECHANICAL CALCULATION
 DOES NOT SHOW THE REQUIRED ,18 CFMS PER SF. HAS BEEN
 ADDED IN. AS PREVIOUSLY REQUESTED, INDICATE ON THE PLAN
 WHAT TYPE OF WORK WILL BE PERFOMED IN THE SHOP AND ALSO
 WHAT TYPE OF EQUIPMENT WILL BE USED. PROVIDE A LAYOUT
 PLAN AND A EQUIPMENT SCHEDULE
  
 4) M1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE THE
 SUPPLY AIR SYSTEMS OF AHU'S 1, 2, 3, 4, 5, 6, & 7-
 SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION
 FOR THE DETECTORS IN THE SUPPLY CAN BE APPLIED IF THE
 MANUFACTURER'S PERFORMANCE DATA INDICATES THE AIR
 HANDLERS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR.
  
 5) M1 & M2: IT APPEARS THAT VEHICLES WILL EITHER DRIVE
 INTO OR BE STORED IN THE "PROPOSED LOADING" AREA WHERE
 THE LARGE BAY DOORS ARE. PROVIDE AN EXHAUST VENTILATION
 SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1 AND SECTION
 404.1 FBC M.
  
 6) M1: PLEASE PLACE A NOTE ON THE PLAN INDICATING THAT
 THE EMERGENCY GENERATOR WILL BE INSTALLED UNDER A
 SEPARATE PERMIT- SECTION 107.2.1 FBC M.
  
 7) M2: PLEASE PROVIDE DIMENSIONED DETAILS OF THE CU
 ACCESS PLATFORMS AND REQUIRED GUARDRAILS AROUND THEM-
 SECTIONS 304.11 SND 306.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  