| 2020-01-28 14:05:28 | 3RD REVIEW: 19110910 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. THE CIVIL SITE PLAN SHOWS A 1000GAL PROPANE |
| | UNDERGROUND GAS TANK THE GAS PLAN SHOWS NATURAL GAS |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. THE GAS ISOMETRIC ON SHEET P1 IS UNCLEAR SHT. L01 |
| | SHOWS THE METER RIGHT OUTSIDE GENERATOR ROOM DOES THE |
| | GALVANIZED SCH 40 PIPING RUN UNDER THE SLAB IF SO IT |
| | SHALL BE SLEEVED THE ENTIRE LENGTH UNDER THE SLAB |
| | PROVIDE DETAIL FOR SLEEVING. PER FBC FG 404.14 |
| | |
| | 3. THE SIZING TABLE FOR CSST IS FOR 2PSI SYSTEM THE |
| | ISOMETRIC DRAWING IS SHOWING THE CSST UPSTREAM OF THE |
| | REGULATOR SO IT SHOULD BE UNDER 2PSI SYSTEM PLEASE |
| | CLARIFY WHICH SIZING TABLE YOU USING TO SIZE THE PIPING |
| | ON THE UNDER 2PSI SYSTEM. PER FBC FG 402.4 |
| | |
| | 4. USING TABLE 402.4(16) FOR 8" WC AS INDICATED ON THE |
| | GENERATOR WITH BTU LOAD OF 1,389,000 3EHD IS |
| | UNDERSIZED. PER FBC FG TABLE 402.4(16) |
| | |
| | 5. PREVIOUS COMMENT PROVIDE MANUFACTURE SPECIFICATION |
| | FOR THE REGULATOR AND ISOLATION CONNECTOR FOR THE |
| | GENERATOR.. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |