| Plan Review Notes For Permit 19110910 |
| Permit Number |
19110910 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-12-19 20:51:01 | PLUMBING 1ST REVIEW**DENIED**19110910 | | | | | | 1) NO GAS REVIEW PERFORMED AS GENERATOR IS REQUIRED TO | | | HAVE A SEPARATE PERMIT PACKET TO INCLUDE THE GEN, SLAB, | | | ELEC, AND GAS SUBMITTED TOGETHER. WPB AMEND 105.1 | | | 2) SHT MP-1 NOTE #1.3 CALLS OUT CONDENSATE LINE AS PVC | | | BUT NOTE 2.3 CALLS OUT COPPER. PLEASE CLARIFY 107.2.1 | | | 3) PLUMBING FLAT AND ISOMETRIC SHOWS OTHER THEN | | | BATHROOM FIXTURES DISCHARGING INTO THE BATHROOM GROUP | | | WET VENT. PLEASE SHOW THESE FIXTURES CONNECTING DOWN | | | STREAM OF THE BATHROOM GROUP WET VENT. FBC-912.1, | | | 912.1.1, 912.2.1 | | | 4) SHOW BREAK ROOM SINK DETAIL SHOWING MAX CABINET | | | HEIGHT AS 34? TO COMPLY WITH FLORIDA ACCESSIBILITY. | | | 5) PROVIDE DIMENSIONS OF ALL NEW ROOMS. FBC 107.3.5 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|