Plan Review Notes
Plan Review Notes For Permit 19110910
Permit Number 19110910
Review Stop G
Sequence Number 1
Notes
Date Text
2020-01-13 09:17:22GAS 2ND REVIEW**DENIED**19110910**
  
 1) PLEASE CLARIFY WHICH KW GENERATOR YOU ARE USE AS
 SHT. S-1 AND P-1 CALL OUT 100KW BUT SHT. SC CALLS OUT
 150KW. PLEASE CLARIFY FBC 107.2.1
 2) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FGC SEC.410.1
  
  
 TIM HUNT
 PLUMBING PLAN REVIEW
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  
  