| Plan Review Notes For Permit 19110910 |
| Permit Number |
19110910 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-13 09:17:22 | GAS 2ND REVIEW**DENIED**19110910** | | | | | | 1) PLEASE CLARIFY WHICH KW GENERATOR YOU ARE USE AS | | | SHT. S-1 AND P-1 CALL OUT 100KW BUT SHT. SC CALLS OUT | | | 150KW. PLEASE CLARIFY FBC 107.2.1 | | | 2) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2017 FGC SEC.410.1 | | | | | | | | | TIM HUNT | | | PLUMBING PLAN REVIEW | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | 561-248-2703 | | | [email protected] | | | | | | |
|