2019-12-20 16:44:54PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PREVIOUS COMMENTS WERE NOT ADDRESSED.
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PREFABRICATED 'AMERICAST' GENERATOR PAD AND
 GENERATOR ANCHORING PLANS FROM 'ENGINEERING EXPRESS'
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ENGINEER
 THAT PREPARED THE DRAWINGS. FAC 61G15-23.003 PROCEDURES
 FOR PHYSICALLY SIGNING AND SEALING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH
 MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 471.025, F.S., AND RULE
 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED
 AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2) THE GENERATOR TABLE THAT IS PROVIDED ON THE
 GENERATOR PAD PLAN DOES NOT LIST THE KOHLER 38RCLB
 MODEL IN THE SPECIFICATIONS THAT WERE SUBMITTED. THE
 KOHLER 38RCL MODEL THAT IS LISTED HAS DIFFERENT
 DIMENSIONS AND WEIGHT. SUBMIT GENERATOR SPECS. AND PAD
 PLANS THAT MATCH. FBC 107.2.1
  
  