| 2019-12-04 08:32:53 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PREFABRICATED 'AMERICAST' GENERATOR PAD AND |
| | GENERATOR ANCHORING PLANS FROM 'ENGINEERING EXPRESS' |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ENGINEER |
| | THAT PREPARED THE DRAWINGS. FAC 61G15-23.003 PROCEDURES |
| | FOR PHYSICALLY SIGNING AND SEALING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN |
| | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, |
| | F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY |
| | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE |
| | USED. |
| | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| | OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE |
| | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| | NOT RENDER THE SIGNATURE ILLEGIBLE. |
| | |
| | 2) THE GENERATOR TABLE THAT IS PROVIDED ON THE |
| | GENERATOR PAD PLAN DOES NOT LIST THE KOHLER 38RCLB |
| | MODEL IN THE SPECIFICATIONS THAT WERE SUBMITTED. THE |
| | KOHLER 38RCL MODEL THAT IS LISTED HAS DIFFERENT |
| | DIMENSIONS AND WEIGHT. SUBMIT GENERATOR SPECS. AND PAD |
| | PLANS THAT MATCH. FBC 107.2.1 |
| | |