Plan Review Notes
Plan Review Notes For Permit 19110813
Permit Number 19110813
Review Stop Z
Sequence Number 1
Notes
Date Text
2020-01-09 12:06:43FAILED
  
 1) PROVIDE THE FULL HEIGHT OF THE GENERATOR, TO INCLUDE
 THE STAND, FUEL TANK AND EXHAUST VENTS AS WELL AS THE
 HEIGHT OF THE GENERATOR ENCLOSURE WALL. THE WALL HEIGHT
 MUST EXCEED THE FULL HEIGHT OF THE GENERATOR.
  
 2) REMOVE THE SITE LIGHTING SHEET FROM THE PERMIT AS
 THIS IS THE GENERATOR PERMIT, NOT THE SITE LIGHTING
 PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]