Plan Review Notes
Plan Review Notes For Permit 19110813
Permit Number 19110813
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-12-09 11:53:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OR PRODUCT SUBMITTALS OF
 THE GENERATOR TYPE NOR FUEL SUPPLY.
  
 PLEASE PROVIDE THE GENERATOR SPECIFICATION SHEETS AND
 FUEL SUPPLY.
  
  
 2) THERE ARE NO INDICATIONS OF WHAT CALSSIFICATION,
 TYPE NOR LEVEL PER NFPA 110, EMERGENCY AND STANDBY
 POWER SYSTEMS
  
 CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY
 SYSTEMS (EPSSS)
 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF
 ELECTRICAL
 POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO
 LOADS FOR
 A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND
 WITHIN A SPECIFIED
 TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER
 SUPPLY
 AS SPECIFIED IN TABLE 4.1(B).
  
 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN
 HOURS, FOR
 WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD
 WITHOUT
 BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).]
 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN
 SECONDS,
 THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE
 TRANSFER
 SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE
 4.1(B)
 PROVIDES THE TYPES DEFINED BY THIS STANDARD.
 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF
 EQUIPMENT
 INSTALLATION, PERFORMANCE, AND MAINTENANCE.
 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE
 OR
 SERIOUS INJURIES.
 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND
 SAFETY.
 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED.
 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT
 ALL LOADS
 SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER
 THAT
 MEETS ALL THE FOLLOWING CRITERIA:
 (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE
 LOAD
 (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED
 IN TABLE
 4.1(A)
 (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED
 IN TABLE
 4.1(B)
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
 3) THERE ARE NO INDICATIONS OF THE EXHAUST SYSTEM.
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME
 MOVER
 BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE
 INDEPENDENTLY
 SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR
 STRESS IS
 APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
 4) THE AREA FOR THE GENERATOR APPEARS TO OUTSIDE THE
 STRUCTURE IN AN ENCLOSURE.
  
 PLEASE CONFIRM THE FOUNDATION IS NOT SEPARATE FROM THE
 MAIN BUILDING SLAB. IF NOT, PLEASE PROVIDE SLAB
 DETAILS.
  
 7.2.2 OUTDOOR EPS INSTALLATIONS.
 7.2.2.1 THE EPS SHALL BE INSTALLED IN A SUITABLE
 ENCLOSURE LOCATED
 OUTSIDE THE BUILDING AND CAPABLE OF RESISTING THE
 ENTRANCE
 OF SNOW OR RAIN AT A MAXIMUM WIND VELOCITY AS REQUIRED
 BY LOCAL BUILDING CODES.
 7.2.2.2 EPSS EQUIPMENT SHALL BE PERMITTED TO BE
 INSTALLED IN
 THE EPS ENCLOSURE.
 7.2.2.3 NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL
 APPURTENANCES,
 EXCEPT THOSE THAT SERVE THIS SPACE, SHALL BE PERMITTED
 IN THE EPS ENCLOSURE.
 7.2.3* LEVEL 1 EPSS EQUIPMENT SHALL NOT BE INSTALLED IN
 THE
 SAME ROOM WITH THE NORMAL SERVICE EQUIPMENT, WHERE THE
 SERVICE
 EQUIPMENT IS RATED OVER 150 VOLTS TO GROUND AND EQUAL
 TO
 OR GREATER THAN 1000 AMPERES.
 7.2.4* THE ROOMS, ENCLOSURES, OR SEPARATE BUILDINGS
 HOUSING
 LEVEL 1 OR LEVEL 2 EPSS EQUIPMENT SHALL BE DESIGNED AND
 LOCATED
 TO MINIMIZE DAMAGE FROM FLOODING, INCLUDING THAT
 CAUSED BY THE FOLLOWING:
 (1) FLOODING RESULTING FROM FIRE FIGHTING
 (2) SEWER WATER BACKUP
 (3) OTHER DISASTERS OR OCCURRENCES
  
 PROVIDE DETAILS.
  
 5) THERE ARE NO MOUNTING DETAILS
  
 7.4 MOUNTING.
 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON
 SOLID
 FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST, OR
 LUBRICATINGOIL
 PIPING AND DAMAGE TO PARTS RESULTING IN LEAKAGE AT
 JOINTS.
 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL
 RAISE THE
 ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE FLOOR OR GRADE
 LEVEL
 AND BE OF SUFFICIENT ELEVATION TO FACILITATE
 LUBRICATING-OIL DRAINAGE
 AND EASE OF MAINTENANCE.
 7.4.2 FOUNDATIONS SHALL BE OF THE SIZE (MASS) AND TYPE
 RECOMMENDED
 BY THE ENERGY CONVERTER MANUFACTURER.
 7.4.3 WHERE REQUIRED TO PREVENT TRANSMISSION OF
 VIBRATION
 DURING OPERATION, THE FOUNDATION SHALL BE ISOLATED FROM
 THE
 SURROUNDING FLOOR OR OTHER FOUNDATIONS, OR BOTH, IN
 ACCORDANCE
 WITH THE MANUFACTURER?S RECOMMENDATIONS AND ACCEPTED
 STRUCTURAL ENGINEERING PRACTICES.
  
 PLEASE PROVIDE DETAILS.
  
  
 6) THERE IS NO INDICATIONS FOR THE NEED OF VENTILATION
 FOR THE PROPOSED GENERATOR AND/OR THE ENCLOSURES'
 ABILITY TO VENTILATE.
  
 7.7 HEATING, COOLING, AND VENTILATING.
 7.7.1* WITH THE EPS RUNNING AT RATED LOAD, VENTILATION
 AIRFLOW
 SHALL BE PROVIDED TO LIMIT THE MAXIMUM AIR TEMPERATURE
 IN THE
 EPS ROOM OR THE ENCLOSURE HOUSING THE UNIT TO THE
 MAXIMUM
 AMBIENT AIR TEMPERATURE REQUIRED BY THE EPS
 MANUFACTURER.
 7.7.1.1 CONSIDERATION SHALL BE GIVEN TO ALL THE HEAT
 EMITTED TO
 THE EPS EQUIPMENT ROOM BY THE ENERGY CONVERTER,
 UNINSULATED
 OR INSULATED EXHAUST PIPES, AND OTHER HEAT-PRODUCING
 EQUIPMENT.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  