| Plan Review Notes For Permit 19110813 |
| Permit Number |
19110813 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-12-17 16:47:53 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. APPLICATION IS FOR A GENERATOR; PLANS SUBMITTED | | | INCLUDE DETAILS WHICH DO NOT APPEAR PERTINENT TO THE | | | GENERATOR INSTALLATION. FOR INSTANCE, SHEET E6.1 | | | INCLUDES SITE LIGHTING POLES. EITHER REMOVE OR CROSS | | | OFF DETAILS NOT APPLICABLE TO THIS PERMIT, FBC 107. | | | | | | 2. FBC B 1609, I WAS UNABLE TO LOCATE A STRUCTURAL | | | DETAIL FOR ANCHORING OF THE GENERATOR. THE DETAIL | | | SHOULD INCLUDE WIND DESIGN CRITERIA. EITHER PROVIDE OR | | | ADVISE ON WHICH PAGE THIS CAN BE FOUND. | | | | | | |
|