2019-12-09 10:31:13 
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19110804
 12/9/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 NFPA 30- 2015
 NFPA 30A- 2015
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PAGE 1: THE VACANT LOT ADJACENT TO THE PROPOSED FUEL
 TANK LOCATION HAS A SEPARATE PCN NUMBER THEREFORE IS A
 LOT THAN CAN BE SOLD OR BUILT UPON. REFER TOTABLES
 22.4.1.1(A) AND 22.4.1.1(B) NFPA 30 AND INDICATE THE
 SEPARATION DISTANCE BETWEEN THE TANK AND THE ADJACENT
 LOT.
  
 2) PROVIDE A COPY OF THE UL CERTIFICATE FOR THE FUEL
 TANK AND A MANUFACTURER'S PRODUCT DATA SHEET- SECTION
 22.2.3 NFPA 30.
  
 3) PAGE 1: REFER TO SECTION 6.2.1 NFPA 30A AND INDICATE
 THE SEPARATION DISTANCES FORM THE FUEL DISPENSERS AND
 THE ADJACENT PROPERTY LINE.
  
 4) PROVIDE COPIES OF THE UL CERTIFICATES AND
 MANUFACTURER'S PRODUCT DATA SHEETS FOR THE FUEL
 DISPENSERS, THE HOSE BREAKAWAY DEVICES, AND AUTO
 SHUTOFF NOZZLES- AND A MANUFACTURER'S PRODUCT DATA
 SHEET- SEE SECTIONS 6.3.2, 6.5.2, AND 6.6.1 NFPA 30A.
  
 5) PAGE 2, NOTE #5: THE LENGTH OF THE DISPENSING HOSE
 SHALL NOT BE GREATER THAN 18'. PLEASE CORRECT THE 20'
 LENGTH SPECIFIED- SECTION 6.5.1 NFPA 30A.
  
 6) PAGE 3: INDICATE THE BOLLARDS WILL BE FILLED WITH
 CONCRETE, AND WILL BE SET NOT LESS THAN 3' DEEP IN A
 CONCRETE FOOTING OF NOT LESS 15 IN. DIAMETER- SECTION
 4.3.7.2 (1) (3) NFPA 30A.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER