Plan Review Notes
Plan Review Notes For Permit 19110762
Permit Number 19110762
Review Stop M
Sequence Number 1
Notes
Date Text
2019-12-05 17:24:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19110762
 12/5/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MECHANICAL PLANS SHOWING ALL REQUIRED
 ALTERATIONS TO THE EXISTING HVAC SYSTEMS TO ACCOMODATE
 THE NEW TENANT BUILD-OUT AND RECONFIGURED FLOOR PLAN.
  
 2) REFER TO SECTION 809.2 FBC EX AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3.1.1 FBC M. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 3) INDICATE HOW EXHAUST VENTILATION IS BEING PROVIDED
 TO THE ALTERED TOILET ROOM- SEE SECTION AND TABLE
 403.3.1.1 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  