| 2019-12-05 17:24:47 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19110762 |
| | 12/5/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE MECHANICAL PLANS SHOWING ALL REQUIRED |
| | ALTERATIONS TO THE EXISTING HVAC SYSTEMS TO ACCOMODATE |
| | THE NEW TENANT BUILD-OUT AND RECONFIGURED FLOOR PLAN. |
| | |
| | 2) REFER TO SECTION 809.2 FBC EX AND PROVIDE MINIMUM |
| | VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER |
| | TABLE 403.3.1.1 FBC M. PROVIDE A SCHEDULE THAT |
| | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR |
| | AIR. |
| | |
| | 3) INDICATE HOW EXHAUST VENTILATION IS BEING PROVIDED |
| | TO THE ALTERED TOILET ROOM- SEE SECTION AND TABLE |
| | 403.3.1.1 FBC M. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |