Plan Review Notes
Plan Review Notes For Permit 19110762
Permit Number 19110762
Review Stop B
Sequence Number 1
Notes
Date Text
2019-12-09 14:38:142017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110762
 ADD: 1177 CLARE AVE. UNIT # 7
 CONT: GENESIS ALLIANCE GROUP
 TEL: 954-973-9694
 E-MAIL:[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 09/ 2019
 ACTION: DENIED
  
 1) PLEASE NOTE THE PROJECT ADDRESS GIVEN 1177 CLARE
 AVENUE DOES NOT MATCH UP WITH THE GIVEN PROPERTY
 CONTROL NUMBER: 74-43-43-28-09-007-0360. THIS ADDRESS
 IS FOR 1141 CLARE AVE. THE OWNERS ADDRESS. PLEASE
 CORRECT THE PROPERTY CONTROL NUMBER TO THE PROJECT
 LOCATION.
  
 2) NOTICE A HOLD HAS BEEN PUT ON THE BUSINESS TAX/
 OCCUPATIONAL LICENSE FOR THIS UNIT UNTIL THE EXPIRED
 PERMITS HAVE BEEN RESOLVED, 05011183, 06082252,
 10070718 & 10110391.
  
 2A) SHEET A-1, THE LIFE SAFETY SHEET INDICATES THE
 ROLL-UP DOOR TO REMAIN. PLEASE NOTE PERMIT 05011183 FOR
 A GARAGE DOOR IS EXPIRED, NEVER FINALED, WILL NEED TO
 BE INCLUDED INTO THIS PERMIT, REFERENCE THE OLD PERMIT
 TO CLEAN UP RECORDS.
  
 2B) SHEET A-1, THE LIFE SAFETY SHEET INDICATES EXISTING
 1 HOUR FIRE RATED SEPARATION WALLS. PERMIT # 06082252
 FOR FIRE RATED WALLS EXPIRED, NEVER FINALED. PERMIT
 10070718 SUBMITTED TO REPLACE PERMIT 06082252 BUT WAS
 NEVER ISSUED, WILL NEED TO BE INCORPORATED INTO THIS
 PERMIT, REFERENCE THE OLD PERMIT TO CLEAN UP RECORDS.
  
  
 2C) SHEET A-1, THE LIFE SAFETY SHEET INDICATES PERMIT
 10110391 NEW FRONT DOORS TRANSOM AND SIDELITES BUT WAS
 NEVER ISSUED, , WILL NEED TO BE INCORPORATED INTO THIS
 PERMIT, REFERENCE THE OLD PERMIT TO CLEAN UP RECORDS.
  
 3) NOTICE. THIS PROPERTY IS IN AN AE FLOOD ZONE-BFE
 12.1 NAVD88. DOCUMENTATION USING THE PALM BEACH COUNTY
 PROPERTY APPRAISERS VALUE OF IMPROVEMENT VALUE
 $877,174.00 DOLLARS IN 2019 AND AN ACCUMULATED VALUE OF
 PERMIT VALUE OF WORK WITHIN THE LAST 5 YEARS OF
 $126,966.00 DOLLARS IN VALUE OR 0.144% OF THE
 IMPROVEMENT VALUE NOT AN SUBSTANTIAL IMPROVEMENT.
 INTERIOR REMODEL ONLY.
  
 4) SHEET A-1 THE LIFE SAFETY PLAN:
  
 4A) UNDER THE LISTING CODE COMPLIANCE DATA, THE PLANS
 STATE THIS IS A MERCANTILE OCCUPANCY (NO CHANGE IN
 OCCUPANCY). THE LAST KNOWN OCCUPANCY TO RECEIVE A
 BUSINESS TAX RECEIPT/ BUSINESS TAX) WAS JUAN AUTO
 REPAIR WHICH WAS CLOSED ON 09/30/2011. THIS WOULD HAVE
 BEEN CLASSIFIED AS A SPECIALTY OCCUPANCY (S1) SEE 2017
 FBC-B SECTION 311.2 & 406.8. THE PLANS SHOULD BE
 DESIGNED TO THE 2017 FBC-EXISTING BUILDING CODE CHAPTER
 10 CHANGE IN OCCUPANCY SECTION 1001.2.2.1PARTIAL CHANGE
 OF OCCUPANCY.
  
 4B) PLEASE NOTE UNDER THE HEADING OF OCCUPANT LOAD YOU
 HAVE TAKEN 30 SQUARE FEET AS THE OCCUPANT LOAD FACTOR.
 IN THE 2017 FBC-BUILDING CODE THIS FUNCTION
 (MERCANTILE) WAS CHANGED TO 60 SQ. FT. GROSS AS AN
 OCCUPANT LOAD FACTOR SEE BLACK LINE IN THE MARGINAL
 MARKINGS. PLEASE CORRECT THE VALUE FOR AN OCCUPANT
 LOAD.
  
 4C) THE TOTAL OCCUPANT LOAD CURRENTLY STATED IS 63
 PERSONS, THIS WOULD REQUIRE 2 EXITS, A IN THE 2017
 FBC-B TABLE 1006.2.1 FOR A MERCANTILE OCCUPANCY WILL
 ONLY ALLOW 49 OCCUPANTS WITH ONE MEANS OF EGRESS. THE
 OCCUPANT LOAD WILL DECREASE WITH THE CORRECT OCCUPANT
 LOAD FACTOR.
  
 4D) SHEET A1 THE LIFE SAFETY PLAN DOES NOT SHOW THE
 FURNITURE LAYOUT WHERE AS SHEET A-2 DOES. NEITHER SHEET
 SHOWS COMPLIANCE WITH THE 2017 ACCESSIBILITY CODE 802.2
 LINES OF SIGHT. PLEASE SHOW IF THE SIGHT LINE WILL BE
 OVERHEAD IN COMPLIANCE WITH 802.2.1.1 OR IN COMPLIANCE
 WITH 802.2.1.2 LINES OF SIGHT BETWEEN HEADS.
  
 4E)(1) THE FLOOR PLAN IDENTIFIES THE DOORS AS D1, D2 OR
 EXISTING TO REMAIN. ALL DOORS NEED TO BE IDENTIFIED.
 DOORS IDENTIFIED AS D1 ARE 34 INCHES WIDE AND DOORS
 IDENTIFIED AS D2 ARE 32 INCHES WIDE. PLEASE SHOW
 COMPLIANCE WITH SECTION 1010.1.1 OF THE FBC-B THE
 REQUIRED CAPACITY OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A MINIMUM CLEAR WIDTH OF 32 INCHES (813 MM).
 CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES. EVEN IF A 2-10 DOOR IS
 MEASURED FROM THE EDGE OF THE DOOR TO THE STOP AT 90
 DEGREES IT WILL BE LESS THAN 32 INCHES.
  
 4E)(2) THE EXISTING DOORS WILL ALSO NEED TO SHOW
 COMPLIANCE WITH THE ACCESSIBILITY CODE FOR 32 INCHES
 CLEAR WIDTH SEE SECTION 404.2.3.
  
 4E)(3) THE QUESTION ABOUT THE DOORS ARE EXISTING, UNDER
 THE DISPROPORTIONATE COST FOR ACCESSIBILITY THE
 BUILDING DEPARTMENT CAN ASK UP TO 20% OF THE VALUE OF
 THE PROJECT FOR ACCESSIBLE UPGRADES OR UP TO $15,514.00
 IN ADDITIONAL COST TO MAKE THE BUILDING CODE COMPLIANT
 FOR ACCESSIBILITY.
  
 DISPROPORTIONATE COST. PLEASE PROVIDE A LETTER EITHER
 FROM THE CONTRACTOR OR DESIGNER OF RECORD ON THEIR
 LETTERHEAD WHERE UP TO 20 % OF THE CONTRACT VALUE IS
 GOING TO BE SPENT IN ACCESSIBLE UPGRADES TO THE
 PROJECT. IF ALL EXISTING CONDITIONS ARE COMPLETED
 (COMPLIED) BEFORE DISPROPORTIONATION COST IS MET A
 LETTER IS NOT REQUIRED. SHOW COMPLIANCE WITH THE:
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 4F) THE FLOOR PLAN DOES NOT INDICATE IF THE FRONT ENTRY
 IS COMPLIANT AS AN ACCESSIBLE ENTRANCE PLEASE SHOW
 COMPLIANCE WITH 303.2 VERTICAL ELEVATION FROM THE
 ACCESSIBLE PARKING SPACE INTO THE BUILDING. 2017
 ACCESSIBILITY CODE 206.2.1. SITE ARRIVAL POINTS.
  
 4G) THE DOOR THAT LEADS INTO ROOM 110 DOES NOT PROVIDE
 THE SIZE OF THE DOOR, AND THE NEW WALL INTO OFFICE 109
 DOES NOT HAVE THE REQUIRED 18 INCHES ON THE LATCH SIDE
 OF THE DOOR. ACCESS CODE 404.2.4.1 FIGURE (A) SWINGING
 DOORS AND GATES. SWINGING DOORS AND GATES SHALL HAVE
 MANEUVERING CLEARANCES COMPLYING WITH TABLE 404.2.4.1.
  
 4H) THE FLOOR PLAN ONLY SHOWS ONE DRINKING FOUNTAIN.
 SPECIAL PROVISIONS INDICATES ONLY ONE DRINKING FOUNTAIN
 IS REQUIRED, THAT 50 % CAN BE SUBSTITUTED WITH A WATER
 DISPENSER. PLEASE REVIEW IN THE 2017 FBC-ACCESSIBILITY
 CODE THE REQUIREMENTS FOR DRINKING FOUNTAINS SECTION.
 2017 FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 4I) THE PLANS INDICATE NEW EXTERIOR WINDOWS AND DOORS.
 WITHIN THE PLANS THERE ARE NO WIND DESIGN CRITERIA.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING, PLEASE PROVIDE IN VASD.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 6.TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 4J) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 4K) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 4L) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5) THE FLOOR PLAN LIST THE RESTROOM AS ROOM 106 AND SEE
 DETAILS ON SHEET A-4. PLEASE NOTE THE DETAILS ON SHEET
 A4 DO NOT PROVIDE THE OVERALL DIMENSIONS OF THE
 RESTROOM NOR DOES THE RESTROOM SHOW COMPLIANCE WITH THE
 ACCESSIBILITY CODE SECTIONS:
  
 WATER CLOSET. 604.3.1 SIZE. CLEARANCE AROUND A WATER
 CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES (1420
 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR WALL.
  
 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
  
 6) THE DETAIL ON SHEET A-4 SHOWS THE WATER CLOSET 1
 FOOT 7 INCHES OR 19 INCHES AWAY FROM THE SIDEWALL TO
 CENTERLINE OF THE WATER CLOSET. PLEASE REVIEW 604.2,
 THE 17 TO 19 INCHES IS ONLY FOR AMBULATORY ACCESSIBLE
 TOILET COMPARTMENTS.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  