2020-03-31 14:25:05PLAN
 REVIEW COMMENTS
  
 FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A103, THE ROOF FRAMING PLAN SHOWS A 4'
 CANTILEVER OVERHANG. A TYPICAL CANTILEVER REQUIRES 2/3
 RDS OF THE BEAM TO BE FIXED INSIDE THE BUILDING AND 1/3
 RD EXTENDED OUTSIDE. THIS IS NOT THE CASE WITH YOUR
 DESIGN. PROVIDE AN ENGINEER'S ANALYSIS ALONG WITH
 DETAILED CONSTRUCTION DRAWINGS FOR THIS CANTILEVER
 DESIGN. FBC 107.2.1.2
  
 2) THE WIND DESIGN INFORMATION ON SHEET A101 SPECIFIES
 ASCE 7 -16. THIS EDITION HAS NOT BEEN ADOPTED IN THE
 2017 FBC. THE CURRENTLY REFERENCED VERSION IS ASCE 7
 -10. FBC-R CHAPTER 46.
  
 3) THE PRODUCT APPROVAL FOR THE FLAT ROOF, FL16709-R6
 FOR THE CERTAINTEED FLINTLASTIC MODIFIED BITUMEN ROOF
 SYSTEM HAS NOT BEEN MARKUP TO INDICATED WHICH OF THE
 SYSTEMS WILL BE USED. SYSTEMS W-4 & W-5 ON PAGES 11 AND
 13 ARE THE ONLY TWO FOR NON-INSULATED ROOFS AS SHOWN ON
 THE PLANS. W-4 IS FOR SELF ADHERED AND W-5 IS FOR HOT
 ASPHALT APPLIED OR TORCH DOWN. MARK THE APPROPRIATE
 ITEMS ON THE PRODUCT APPROVAL. FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.