| 2019-12-19 15:42:36 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19110754 |
| | 12/19/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) TABLE R402B ON PAGE 2 OF THE ENERGY FORM R402-2017 |
| | HAS NOT BEEN FILLED OUT. THE LANGUAGE ON THE FORM |
| | STATES "TO COMPLY, A BUILDING MUST MEET OR EXCEED ALL |
| | OF THE ENERGY EFFICIENCY REQUIREMENTS ON TABLE R402A |
| | AND ALL APPLICABLE MANDATORY REQUIREMENTS SUMMARIZED IN |
| | TABLE R402B OF THIS FORM." IN TABLE R402A PLEASE |
| | PROVIDE THE INSTALLED VALUES FOR THE WINDOWS, THE DOOR, |
| | THE WALL AND AND CEILING INSULATIONS, THE DUCT R-VALUE, |
| | AND THE AC SYSTEM, MANDATORY REQUIREMENTS CHECKLLIST- |
| | TABLE R402B WAS NOT PROVIDED WITH THE FORM SUBMITTAL. |
| | |
| | 2) THE AC CALCULATIONS ARE INDICATING THE FRONT DOOR IS |
| | FACING EAST, HOWEVER ACCORDING TO PALM BEACH COUNTY |
| | RECORDS THE FRONT DOOR IS FACING NORTH- PLEASE REVISE |
| | THE CALCULATIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |