| 2019-12-17 15:25:54 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19110754 |
| | REVIEWED: DECEMBER 17, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: |
| | GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN |
| | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| | SHALL COMPLY WITH SECTION R502. UNALTERED PORTIONS OF |
| | THE EXISTING BUILDING OR BUILDING SUPPLY SYSTEM SHALL |
| | NOT BE REQUIRED TO COMPLY WITH THIS CODE. |
| | -PLEASE PROVIDE DOCUMENTATION OF HOW YOU ARE COMPLYING |
| | WITH ENERGY CODE. EITHER PRESCRIPTIVE(502.1.1), |
| | SIMULATED(R502.1.2) OR ENERGY RATING INDEX(502.2.1.3) |
| | |
| | 2) 107.5.3 FBC[AMENDED]PLEASE ADD ROOF SLOPE TO PLANS. |
| | PROVIDE PRODUCT APPROVALS FOR FLAT ROOF, OR INDICATE |
| | THAT THEY WILL BE PROVIDED WITH THE SUB-PERMIT |
| | APPLICATION. |
| | |
| | 3) 403.4 FBC[R] EXTERIOR FOOTINGS SHALL BE PLACED NOT |
| | LESS THAN 12 INCHES BELOW THE UNDISTURBED GROUND |
| | SURFACE. WHERE APPLICABLE, THE DEPTH OF FOOTINGS SHALL |
| | ALSO CONFORM TO SECTIONS R403.1.4.1 THROUGH R403.1.4.2. |
| | |
| | 4) 806.3 FBC[R] VENT AND INSULATION CLEARANCE. WHERE |
| | EAVE OR CORNICE VENTS ARE INSTALLED, INSULATION SHALL |
| | NOT BLOCK THE FREE FLOW OF AIR. NOT LESS THAN A 1-INCH |
| | (25 MM) SPACE SHALL BE PROVIDED BETWEEN THE INSULATION |
| | AND THE ROOF SHEATHING AND AT THE LOCATION OF THE VENT. |
| | -SECTION A/3 SHOWS 2X8 RAFTERS WITH R30 BATT. PLEASE |
| | REVIEW HOW R-30 BATT WOULD FIT IN THE CAVITY AND LEAVE |
| | 1 INCH MINIMUM AT SHEATHING FOR VENTING. ALSO, NOTE |
| | SAYS VENT TO MATCH EXISTING. SINCE EACH RAFTER CREATES |
| | ISOLATED SPACE PLEASE CALL FOR A CONTINUOUS SOFFIT |
| | VENT. |
| | |
| | IF AN UNVENTED SPACE IS USED DUE TO CONSTRAINTS, THAN |
| | PLEASE REVIEW SECTION 806.5 FOR AIR PERMEABLE |
| | INSULATION NEEDING RIDGID BOARD INSULATION ABOVE |
| | SHEATHING. |
| | |
| | 5) 806.5 FBC[R] UNVENTED ATTIC AND UNVENTED ENCLOSED |
| | RAFTER ASSEMBLIES. 5.1.2. WHERE AIR-PERMEABLE |
| | INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL |
| | ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH |
| | SECTION 5.1.1. IN ADDITION TO THE AIR-PERMEABLE |
| | INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL |
| | SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE |
| | INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING |
| | IN ACCORDANCE WITH THE R-VALUES IN TABLE R806.5 FOR |
| | CONDENSATION CONTROL. |
| | |
| | IF SPRAY INSULATION IS APPLIED TO ROOF DECK THAN NO |
| | VENTING OR INSULATION FOR CONDENSATION CONTROL IS |
| | NEEDED, BUT PROVIDE CUT SHEET FOR ICYNENE(ICC-ES REPORT |
| | OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH THICKNESS |
| | NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD INDEX AND |
| | SMOKE DEVELOPED INDEX. |
| | |
| | 6) 318.1 FBC[R] TERMITE PROTECTION. TERMITE PROTECTION |
| | SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING |
| | SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND |
| | PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS |
| | OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE |
| | TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202, |
| | ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE |
| | APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A |
| | CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE |
| | BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL |
| | COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE |
| | BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE |
| | PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN |
| | ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE |
| | FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER |
| | SERVICES.? |
| | -ADD NOTE TO PROVIDE TERMITE PROTECTION. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |