| Plan Review Notes For Permit 19110738 |
| Permit Number |
19110738 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-18 18:59:25 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SYSTEM NUMBER W-2 ON PAGE 2 OF 3 OF PRODUCT | | | APPROVAL FL9487-R5 FOR WOOD DECKS WITH MECHANICALLY | | | ATTACHED INSULATION AND BONDED ROOF COVER HAS A MAXIMUM | | | DESIGN PRESSURE OF -82.5 PSF. THIS TWO STORY BUILDING | | | IS LOCATED IN EXPOSURE CATEGORY C WITH A VULT WIND | | | SPEED OF 170 MPH. THE UPLIFT FOR ROOF ZONE 3 (CORNERS) | | | IS -102 PSF AND EXCEEDS THE MAXIMUM DESIGN PRESSURE OF | | | THE SPECIFIED SYSTEM. | | | |
|