| Plan Review Notes For Permit 19110717 |
| Permit Number |
19110717 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-12-17 14:49:03 | FAILED | | | | | | PLEASE PROVIDE WRITTEN RESPONSE. | | | | | | 1) THE REVISION IS FOR THE REMOVAL OF THE FIRE PUMP AND | | | FIRE PUMP ROOM, YET A SHEET HAS BEEN INSERTED FOR THE | | | DECK FRAMING PLAN, THE DECK, THE DECK DETAILS AND THE | | | DECK SECTION. THESE ITEMS ARE NOT PART OF THE BUILDING, | | | SO THEY NEED TO BE SUBMITTED AS A SEPARATE DECK PERMIT, | | | WHICH ACCURATELY SHOWS THE VALUE OF THE DECK. NOTE: | | | ZONING MADE PROVIDED THE COMMENT THAT THE DECK REQUIRES | | | A SEPARATE PERMIT AS PART OF THE BUILDING REVIEW. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | | | | | | | |
|