| Plan Review Notes For Permit 19110717 |
| Permit Number |
19110717 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-18 11:09:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE REVISION APPLICATION INDICATED "ELIMINATE FIRE | | | PUMP AND FIRE PUMP ROOM" | | | | | | THERE IS VIRTUALLY NO INFORMATION REGARDING THE FIRE | | | PUMP NOR FIRE PUUMP ROOM AON THE SUBMITTED PLAN SHEETS. | | | THERE IS SITE WORK, ROOF DECK, HVAC, ELECTRICAL, DOOR | | | SCHEDULE, ETC, HOWEVER, NO FIRE PUMP/ROOM. | | | | | | PLEASE REVIEW AND CORRECT OR CLARIFY. | | | | | | | | | 2) THE ARE NO HYDRAULIC CLACULATIONS OR OTHER SIGNED | | | AND SEALED ENGINEERENING REVIEW DOCUMENTATION | | | INDICATING THAT A FIRE PUMP IS NOT REQUIRED. | | | | | | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILED INFORMATION | | | SIGNED AND SEALED BY A ENGINEER FOR OFFICIAL REVIEW. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|