| Plan Review Notes For Permit 19110715 |
| Permit Number |
19110715 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-01 11:07:24 | JAKE LEAHY ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | SECONDARY CONDUCTORS OF THE TRANSFORMER ARE THEY 10' OR | | | 25' PER 240.21? IF MORE THAN 10 OR 25' THEY WILL NEED A | | | DISCONNECT AT THE TRANSFORMER LOCATION. |
|