Plan Review Notes
Plan Review Notes For Permit 19110703
Permit Number 19110703
Review Stop M
Sequence Number 2
Notes
Date Text
2020-02-10 12:43:462ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19110703
 2/10/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1ST REVIEW COMMENTS PRINTED BELOW STILL EXIST- PLEASE
 COMPLY.
  
 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED FOR REVIEW-
 SECTION 107.2.1 WPB.
  
 2) PLEASE IDENTIFY THE LARGE ROOM ON THE SUBMITTED
 OWNER/BUILDER PLAN- SECTION 107.2.1 WPB.
  
 3) INDICATE HOW THE LARGE ROOM WILL BE VENTILATED-
 NATURALLY OR MECHANICALLY. IF USING NATURAL SHOW
 COMPLIANCE WITH SECTION R303.1 FBC RES AND VERIFY THE
 OPENABLE AREA (WINDOWS, DOORS) TO THE OUTDOORS IS NOT
 LESS THAN 4 PERCENT OF THE FLOOR AREA BEING VENTILATED.
  
 4) REFER TO SECTION R303.10 FBC RES AND INDICATE HOW
 HEATING WILL BE PROVIDED TO THE NEW ADDITION. PLEASE
 NOTE THAT PORTABLE SPACE HEATERS SHALL NOT BE USED TO
 ACHIEVE COMPLIANCE.
  
 5) REFER TO SECTION R303.3 AND INDICATE HOW THE
 BATHROOM WILL BE VENTILATED- NATURALLY THROUGH AN
 OPERABLE WINDOW OR MECHANICALLY PER SECTION M1507 FBC
 RES.
  
 6) THE CONVERSION OF THE GARAGE INTO HABITAL,
 CONDITIONED SPACE IS CLASSIFED AS BOTH AN ADDITION AND
 A CHANGE OF OCCUPANCY PER SECTIONS R202, R503.2, AND
 R505.2 FBC EC. PLEASE PROVIDE AN ENERGY COMPLAINCE
 REPORT IN ACCORDANCE WITH SECTION R101.5.1.1 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  