| Plan Review Notes For Permit 19110703 |
| Permit Number |
19110703 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-02-04 13:52:19 | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE LABEL EACH ROOM SHOWN ON THE FLOOR PLAN. FBC | | | WPB AMENDMENTS 107 | | | 2) PLEASE SHOW THE REQUIRED EMERGENCY EGRESS FROM | | | SLEEPING ROOMS. PER FBC R310 | | | 3) PLEASE PROVIDE STRUCTURAL DETAILS FOR THE CLOSING UP | | | OF THE OVERHEAD GARAGE DOOR. FBC WPB AMENDMENTS 107 | | | 4) PLEASE PROVIDE WIND LOAD CALCULATIONS OR SIGNED AND | | | SEALED DETAILS FROM AN ARCHITECT OR ENGINEER. FBC | | | R301.1.3 | | | 5) PLEASE SHOW ON THE DRAWINGS THE WIND DESIGN | | | PARAMETERS USED (CODE VERSION, WIND SPEED, ETC.) PER | | | FBC R301.2.1.1 - FBC 1609.1.1 | | | 6) PLEASE SHOW NEW WINDOW SIZES. FBC WPB AMENDMENTS107 | | | 7) PLEASE SHOW THE WALL AND CEILING INSULATION TYPE AND | | | "R" VALUE TO COMPLY WITH FBC ENERGY R402 | | | 8) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND | | | INSTALLATION INSTRUCTIONS) PRODUCT APPROVALS FOR THE | | | NEW EXTERIOR WINDOWS. FBC R301.2.1.2 | | | |
|