| 2019-12-03 10:14:46 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 19110703 4101 GARDEN AVE |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | RE: PLUMBING RISER |
| | 1. PER WPB FBC 107.2.1, A CODE COMPLIANT PLUMBING RISER |
| | DIAGRAM SHALL BE PROVIDED SHOWING ALL FIXTURE DRAINS |
| | WITH TRAPS (EXCEPT THAT THE WATER CLOSET AS AN |
| | INTEGRALLY TRAPPED FIXTURE SHALL NOT SHOW A TRAP), |
| | FIXTURE BRANCHES AND BUILDING DRAIN. ALL COMPONENTS |
| | SHALL BE SIZED. DRAWING SHALL COMPLY WITH FBC RES |
| | CHAPTERS 30 AND 31. |
| | 2. THE KITCHEN SINK SHALL CONNECT DOWNSTREAM OF THE |
| | BATHROOM FIXTURES PER FBC RES P3108.1. |
| | 3. AT LEAST ONE VENT SHALL BE EXTENDED TO THE BUILDING |
| | EXTERIOR IN ACCORDANCE WITH FBC RES P3102.1. |
| | 4. THE BUILDING SEWER SHALL CONNECT TO A SEWER LATERAL |
| | PROVIDED BY WPB PUBLIC UTILITIES OR TO THE EXISTING |
| | BUILDING SEWER SERVICING THE MAIN HOUSE. CONFIRM |
| | ELEVATIONS WILL ALLOW GRAVITY DRAIN. |
| | 5. PER WPB FBC 107.2.1, SHOW LOCATION, SIZE AND TYPE OF |
| | WATER HEATER ON FLOOR PLAN. |
| | 6. PER WPB FBC 107.2.1, DRAWINGS SHALL HAVE THE PRINTED |
| | NAME AND SIGNATURE OF THE DESIGNER. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19110703 4101 GARDEN AVE |
| | |
| | |
| | |
| | |