| 2019-12-10 15:39:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE, SHOWING |
| | ALL DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR |
| | OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE |
| | AND FEED TO ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, |
| | SHOW INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, |
| | 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; WPB FBC 107.2.1 |
| | 2. PLAN SHOWS SEVERAL CIRCUITS GOING TO APARTMENT. A |
| | BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A BRANCH |
| | CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE |
| | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE |
| | FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC |
| | 225.30 |
| | 3. PANEL SCHEDULE SHOWS A 125 AMP MAIN ON A 100 AMP |
| | PANEL. THIS PANEL IS NOT RATED FOR 125 AMPS. PROVIDE |
| | CORRECTION. NEC 110.3, 408.30 |
| | 4. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, |
| | 801.2, OR 901.2 AS APPLICABLE. |
| | 5. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF |
| | PLAN IS REQUIRED TO BE SIGNED BY THE PERSON RESPONSIBLE |
| | FOR THE DESIGN. EACH SHEET SHOULD ALSO SHOW THE ADDRESS |
| | OF THE PROJECT. PROVIDE CORRECTION. WPB FBC 107.1; FS |
| | 471/481 |
| | 6. PROVIDE ACCURATE LOAD CALCULATION FOR EXISTING |
| | SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM |
| | CAPACITY OF SERVICE IS ADEQUATE. LOAD CALCULATION |
| | SHOULD BE IN COMPLIANCE WITH FBC RE 3602.2. NEC 215.2, |
| | 220, 408.30; FBC RE E3602.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |