| Date |
Text |
| 2019-12-16 11:21:28 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19110703 |
| | REVIEWED: DECEMBER 16, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 107.5.3 FBC[AMENDED] 107.2.1FBC[AMENDED] ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | -PLEASE ADD NAME OF PERSON ON EACH PAGE PROVIDED. I SEE |
| | SIGNATURE ON ONE SHEET ONLY, BUT NAME AND SIGNATURE |
| | SHOULD BE ON ALL PAGES. |
| | |
| | 2) PROVIDE A DESCRIPTION AND NOTES OF WORK BEING |
| | PERFORMED ON THE PLAN. IT IS HARD TO TELL THE EXTENT OF |
| | WORK WITH THE DRAWING PROVIDED. FOR EXAMPLE, ARE THE |
| | EXTERIOR WALLS BEING DRYWALLED, INSULATION |
| | CEILING/WALLS AND WHAT ARE NEW PARTITIONS MADE FROM? |
| | |
| | 3) ADD SOME PROJECT DATA TO THE PLANS: |
| | SQ. FOOTAGE OF AREA OF WORK |
| | DIMENSIONS OF NEW ELEMENTS |
| | WIND DESIGN CRITERIA |
| | OCCUPANCY (R3) |
| | |
| | 4) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: |
| | GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN |
| | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| | SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED |
| | PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY |
| | SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE. |
| | -HOW ARE ENERGY CODE REQUIRMENTS BEING IMPLEMENTED IN |
| | THIS PROJECT? |
| | |
| | 5) 107.2.5 FBC[AMENDED] DEMOLITION PLAN. |
| | - PROVIDE DEMOLITION PLAN TO SHOW EXISTING |
| | CONFIGURATION, OPENINGS BEING FILLED AND NOTES ON WHAT |
| | IS BEING DEMOED. |
| | - PROVIDE DETAILS TO SHOW HOW OPENINGS ARE BEING FILLED |
| | IN. |
| | |
| | 6) PROVIDE PRODUCT APPROVALS FOR ANY NEW DOORS OR |
| | WINDOWS. SHOW ON PLANS WHERE NEW DOORS OR WINDOWS ARE |
| | BEING INSTALLED AND THE SIZES OF OPENINGS. |
| | |
| | 7)IS ANTHING HAPPENING WITH THE ROOF? IF SO PROVIDE |
| | PRODUCT APPROVALS FOR ROOFING, OR INDICATE THAT THEY |
| | WILL BE SUBMITTED WITH ROOFING SUB-PERMIT |
| | |
| | A FULL REVIEW WILL BE PROVIDED UPON RECEIPT OF MORE |
| | COMPLETE DRAWINGS, NOTES AND DESCRIPTIONS. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |