| Date |
Text |
| 2019-11-18 09:21:37 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE PLANS SUBMITTED FOR REVISION DO NOT EXIST IN THE |
| | CURENT APPROVED DRAWINGS ON FILE. THE ENGINEER OF |
| | RECORD (EOR), SHOWN AS L J SAMADI PE, MUST PROVIDE ANY |
| | REVISED DOCUMENTS WITH THE PROPER SIGNATURE AND SEAL |
| | PER FLORIDA STATUTES. PROVIDE CORRECTION. WPB FBC |
| | 107.1, 107.2.1; FS 471 |
| | 2. THE LOAD CALCULATION PROVIDED DOES NOT MATCH THE |
| | ORIGINAL PROVIDED BY THE EOR. IF THE LOADS HAVE |
| | CHANGED, PROVIDE DOCUMENTATION TO SUPPORT THESE |
| | CHANGES. THE LOAD CALCULATION PROVIDED IS NOT CODE |
| | COMPLIANT. ALSO, A LOAD CALCULATION FOR THE ENTIRE |
| | SERVICE IS REQUIRED, IN ADDTION TO THE ONE PROVIDED FOR |
| | THE RESIDENTIAL UNIT, TO CONFIRM THE CAPACITY IS |
| | SUFFICIENT. PROVIDE CORRECTION. NEC 220 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |