| Plan Review Notes For Permit 19110669 |
| Permit Number |
19110669 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-11-23 11:19:10 | PERMIT #19110669 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | | | | BRITTANY WOODS | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4754 | | | | | | PROVISO | | | | | | SHALL COMPLY WITH NFPA 72, NFPA 1 FIRE CODE AND NFPA | | | 101 LIFE SAFETY | | | | | | FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED AND | | | IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER | | | LOCK FOR DEDICATED BRANCH CIRCUIT. | | | | | | | | | PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE | | | NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN | | | THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE | | | BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR. | | | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | |
|